background image

 
 
 
 

 

 

TECHNICAL DATA SHEET 02/2018 - ENG

 

ICMA S.p.a. via Garavaglia, 4   20012 Cuggiono (MI) – ITALIA 
 Tel. +39 02 97249134 / +39 02 97249135   

www.icmaspa.it

 e-mail: 

[email protected]

 

 

pag. 5 

ART. S001-S002-S003-S004   SOLAR MODULE

 

 

 

TECHNICAL SPECIFICATIONS

 

 

The  solar modules receive a signal from the external controller which,  having  at least two temperature sensors (one is 
positioned on the panel outlet pipe and the other is an immersion sensor in the boiler), constantly reads  the temperature 
difference and keeps it within the established range, which normally varies between 5 and 8 °C. If the 

Δt between the panel and 

the boiler is found to be over the established set point, the controller starts up the pump on the module to provide the lacking 
thermal load. If, on the other hand, the 

Δt is narrower than the one set, the internal pump will be disabled. 

For further clarification about the electronic controller functioning, consult the technical documentation about art. S301, S302 and S302PWM. 

 

FILLING THE SYSTEM 

 

1.

 

Open the shut off valves connected with the air vent valves A (Fig.1). These valves must be located at the highest point 
of the system to optimize their function of air expulsion from the circuit. 

2.

 

Open both the shut off valves 4 (Tab.1) and 7 (when present) turning their handles to 45° (see the operating specifications 
of these valves on page 11 of this data sheet). 

3.

 

Fully open the flow meter 6 (Tab. 1) carrying the reference mark of the flow meter in vertical position (see operating 
specifications on page 10). Check that the drain tap 3 is closed. 

4.

 

Connect an external pump to the tap 3 of the instrument holder connection 2 (Tab.1) with a rubber pipe. This pump will 
get the heat-transfer fluid, previously prepared, from an external container. 

5.

 

Open the tap 3 of the instrument holder connection 2 (Tab.1) and start the external pump to fill the system. 

6.

 

Fill the system until air stops coming out of the air vent valves A (Fig.1). 

7.

 

Close the tap 3 and disconnect the external pump. 

8.

 

Close the shut off valves connected with the air vent valves A (Fig.1). 

 
 

 
 

 
 
 
 
 
 
 
 
 
 
 

 

 

 

WASHING THE SYSTEM 

 

1.

 

Open both the shut off valves 4 (Tab.1) and 7 (when present) turning their handles to 45° (see the operating specifications 
of these valves on page 11 of this data sheet). 

2.

 

Close the flow meter 6 (Tab. 1) carrying the reference mark of the flowmeter in horizontal position (see operating 
specifications on page 10).  

3.

 

Connect the drain cock 3 of the flow meter 6 (Tab. 1) to a point of discharge using a rubber pipe. 

4.

 

Connect an external pump to the tap 3 of the instrument holder connection 2 (Tab.1) with a rubber pipe. This pump will 
get the washing liquid (or the new heat-transfer fluid) from an external container. 

5.

 

Start the external pump and open both taps 3, the washing fluid will enter into the system while the one inside will be 
discharged through the lower tap 3 of the flow meter 6 (Tab. 1). 

6.

 

Open slightly and for a short time the flow meter 6 (Tab. 1) to let the washing fluid running also through the system pump.  

7.

 

For a proper washing let the pump running for a few minutes, then close the taps, switch off the pump and disconnect the 
rubber pipes. 

Fig.1 

Summary of Contents for S001

Page 1: ...olar modules are employed in the primary circuits of solar systems to manage the thermodynamic cycle of the heat transfer fluid between the solar panels and the hot water storage tank The S003 S004 modules are also equipped with electronic controllers which through a sophisticated monitoring system and safety functions ensure the total protection of the system during its operation PRODUCT RANGE S0...

Page 2: ...s and are equipped with a circulator pump having proper performances flow and head as well as several regulation and control devices that run the operation of the circuit TECHNICAL SPECIFICATIONS Performance Fluids used Water and glycol solutions Maximum percentage of glycol 50 Maximum operating pressure 10 bar Calibration of safety valve 6 bar Permitted temperature range 10 C 160 C Max ambient te...

Page 3: ...nection with manometer 3 Taps for filling emptying and washing the system 4 Shut off valve with thermometer and built in check valve 5 Circulator 6 Flowmeter 7 Shut off valve with thermometer and built in check valve 8 Deaerator 9 Preformed insulating base 10 Hose connection 11 Preformed insulating cover 12 Inspection compartment insert 13 Pump connector 14 Cable duct groove 15 Electronic controll...

Page 4: ...maspa it e mail sales icmaspa it pag 4 ART S001 S002 S003 S004 SOLAR MODULE DIMENSIONS S002 S001 S003 S004 CODE A B C D E F G H I L WEIGHT KG S001 G M 100 140 325 480 420 260 60 60 170 7 0 S002 G M 140 275 480 420 235 40 60 170 5 0 S003 G M 100 140 480 480 420 260 60 60 170 7 5 S004 G M 140 360 480 420 235 40 60 170 5 5 Tab 2 ...

Page 5: ...on see operating specifications on page 10 Check that the drain tap 3 is closed 4 Connect an external pump to the tap 3 of the instrument holder connection 2 Tab 1 with a rubber pipe This pump will get the heat transfer fluid previously prepared from an external container 5 Open the tap 3 of the instrument holder connection 2 Tab 1 and start the external pump to fill the system 6 Fill the system u...

Page 6: ...to the system follow the instructions of the solar panels manufacturer 11 After a few hours of operation remove air from the solar system once again with the air vent valves A Fig 1 and the deaerator 8 Tab 1 when present After all air has been removed check once again the pressure in the system with the manometer 2 Tab 1 and if necessary restore the desired operating value as described above in st...

Page 7: ...eristics Technical specifications Brand Grundfos Model Solar 15 65 Centre to centre distance 130 mm Connections G1 M Electrical power supply 230V 50 60Hz Operating temperature 2 110 C Max temperature 140 C per brevi periodi Max operating pressure 10 bar Protection level IP44 Energy class EEI C Technical specifications Brand Wilo Model Solar ST20 6 Centre to centre distance 130 mm Connections G1 M ...

Page 8: ...and Wilo Model Yonos PARA ST 15 6 RKC Centre to centre distance 130 mm Connections G1 M Electrical power supply 230V 50 60Hz Operating temperature 2 110 C Max temperature 130 C per brevi periodi Max operating pressure 10 bar Protection level IPX4D Energy class EEI 0 21 Technical specifications Brand Grundfos Model UPM3 SOLAR 15 75 130 Centre to centre distance 130 mm Connections G1 M Electrical po...

Page 9: ...LE ARTICLE S164 Circulator with 3 constant curves ΔP variable 2 PWM curves Hydraulic characteristics Technical specifications Brand Wilo Model Yonos PARA RSTG 15 7 5 RK Centre to centre distance 130 mm Connections G1 M Electrical power supply 230V 50 60Hz Operating temperature 2 110 C Max temperature 130 C per brevi periodi Max operating pressure 10 bar Protection level IPX4D Energy class EEI 0 21...

Page 10: ...possible to read in real time the value of the flow in the circuit with the flow indicator Fig 3 This device is equipped with a glass having a graduated rate of flow scale with a calibration spring and with a movable indicator that varies its position according to the flow inside the glass The flow rate reading are explained the paragraph below The flow meter is also equipped with a manual flow re...

Page 11: ... are equipped with a deaerator 8 Tab 1 During the normal functioning of the solar circuit the air present in the heat transfer fluid is separated and collected in the upper part of the deaerator During the start up the air collected in the deaerator has to be periodically discharged by the manual air vent located in the upper part of the deaerator by turning its spindle counter clockwise with a sc...

Page 12: ...onditions and limits on operating valves described in this information sheet SAFETY STANDARDS FOR ASSEMBLY AND INSPECTION Assembly and inspection operations must always be performed by qualified authorised personnel familiar with the instructions contained herein Make sure the system is shut down before performing any work on it ELECTRICAL CONNECTIONS Electrical connections must be made by qualifi...

Reviews: