7. Auxiliary Delay ON
– (0-30 minutes) – Set the delay time in minutes for
auxiliary heat to be locked out after a call for second stage . This extra
savings feature is used to temporarily lock out auxiliary heat devices,
allowing just heat pump to try to satisfy heat call .
Press the
up
or
down
button to select .
Press
the
right
button to advance to the next screen .
8 .
Lockout (0-8°, NITE, COOL-HEAT) –
Select the number of degrees set
temperature can be changed during keypad lockout or select to lockout
during
NITE
period only .
COOL-HEAT
lockout allows adjustment of the set
temperatures to the maximum heat set temperature selected in Step 9 and
minimum cool set temperature selected in Step 10 .
Note:
The mode cannot be changed when the thermostat is locked .
Press the
up
or
down
button to select .
Press the
right
button to advance to the next screen .
9 .
Maximum Heat Setpoint
(45°F to 90°F) (7°C to 32°C)
Adjust to control the maximum heat set temperature allowed .
Press the
up
or
down
button to select .
Press the
right
button to advance to the next screen .
10 .
Minimum Cool Setpoint
(45°F to 90°F) (7°C to 32°C)
Adjust to control the minimum cool set temperature allowed .
Press the
up
or
down
button to select .
Press the
right
button to advance to the next screen .