4 .
Staged Off Outputs
Select whether the outputs for heating and cooling are staged off
independently or are satisfied simultaneously .
1 = outputs staged off independently
0 = outputs off simultaneously
Press the
up
or
down
button to set .
Press the
right
button to advance to the next screen .
5 .
Minimum Deadband
(1°F to 9°F) (1°C to 5°C)
Set the minimum separation between heat setpoint and cool setpoint in
Auto Changeover
Mode .
Press the
up
or
down
button to set deadband value .
Press the
right
button to advance to the next screen .