Residual Risk Management
27
5
Residual Risk Management
EXCESSIVE STEAM PRESSURE
–
Make sure the safety valves properly open at the design pressure.
–
It is necessary to check the correct activation of the shut-off pressure switch that eliminates the cause of pressure increase by
stopping the burner.
–
The matching between the boiler maximum flow thermal and the actual burned maximum power must be checked.
ACCESSORY SUITABILITY
–
Match accessories according to what provided for by the reference standards EN12953-6
OVERHEATING DUE TO LOW WATER LEVEL
–
The correct operation of the safety level switch must be checked in accordance with the indications set forth in the technical
manual.
–
It is necessary to check that the operating water conductivity values are within those provided in the supplied technical
manual. (EN 12953-10)
–
Make sure the water loading pump is working properly as described in the technical manual provided with the boiler (pump
wear, hydrostatic head in suction, water supply temperature, pump connection/disconnection from the level control probes).
OVERHEATING DUE TO SCALE BUILD-UPS
–
Analyse water at the required frequency intervals, making sure that the values are within the limits specified in the technical
manual and performing the suitable treatments. (EN 12953-10)
TURBULENCES IN THE WATER LEVEL
–
Check that the characteristics of the delivery and operating water of the boiler correspond to those indicated in the Technical
Manual (EN 12953-10)
WATER CONDUCTIVITY
–
Water delivery has to be checked and kept within the limit values declared in the instruction manual and prescribed by EN
12953-10, according to a suitable treatment with filtering, softening and conditioning processes of the mains water (specified
on the user's manual and under the user's responsibility).
–
Carry out operational tests of the safety devices at the times and with methods specified in the manuals.
FOAMS
–
Check that the characteristics of the delivery and operating water of the boiler correspond to those indicated in the Technical
Manual (EN 12953-10)
CAUSTIC EMBRITTLEMENT
–
Carry out water analysis at the necessary time intervals (refer to user's manual).
–
Perform water treatments in order to bring the characteristic values back within the limits specified in the use and
maintenance manual (EN 12953-10)
–
Blowdown by working on the drain valves present on boiler bottom.
ACID CORROSION
–
Carry out water analysis at the necessary time intervals (refer to user's manual).
–
Perform water treatments in order to bring the characteristic values back within the limits specified in the use and
maintenance manual.