General information
15
TECHNICAL DATA
DESCRIPTION
u.m.
ECOVAPOR
350
500
650
800
1000
1350
1700
2000
2500
3000
Useful nominal power
[1]
kW
238
341
443
545
681
920
1158
1363
1703
2044
Nominal thermal flow
kW
254
362
471
580
725
979
1232
1450
1812
2175
Minimum nominal power
kW
30
43
55
68
85
115
145
170
213
256
Minimum thermal flow
kW
31
44
58
71
89
120
151
177
222
266
Efficiency at 100% (ref. P.C.I.)
[1]
%
94
Furnace depression (Flue gas pressure drop)
mbar
n.a.
-32
n.a.
Rated pressure
bar
12-15
Total capacity
l
921
1250
1830
2190
2640
3050
3380
4020
Capacity at level
l
673
950
1280
1475
2000
2300
2490
2825
EXCHANGE surface
m
2
8,30
12,80
14,20
22,30
25,00
31,5
40,5
48
Steam production
[1]
kg/h
350
500
650
800
1000
1350
1700
2000
2500
3000
Rated frequency ~ voltage
Volt /Hz
400/50
Electric protection rating
IP
IP55
Absorbed power
kW
6
7
9
14,5
15,5
19,5
Allowed fuels
Natural gas
Lower calorific value
MJ/m
3
34,2
Max. / min. fuel pressure values
mbar
17,25
Fuel nominal flow rate (G max gas flow rate)
Stm
3
/h
26,85
38,35
49,86
61,37
76,71
103,56
130,40
153,42
191,77
230,12
Minimum fuel flow rate
Stm
3
/h
3
4
5
6
8
10
Flue gas temperature at nominal power
°C
135
135
135
135
135
135
135
135
135
135
Total weight
kg (12 bar
version)
2180
2180
2550
2550
3240
3690
4400
5250
5920
6320
[1]
80 °C treated water feed temperature.
SAFETY COMPONENT CALIBRATIONS
The components listed below are adjusted at the indicated pressure values
–
safety valve: 12 bar (factory sealed - do not modify)
–
safety pressure switch: 11 bar (factory sealed - do not modify)
–
pressure transducer: 10 bar (adjust during installation, if necessary).
COMPONENTS
The steam generating systems
ECOVAPOR
feature a series of components that can be divided into:
–
Safety components (safety valves, safety level switches, safety pressure switch).
–
Indicators (level indicator, manometer, flame light).
–
Adjustment components (level adjusters, pressure switches, pressure transducers).
–
Feed components (centrifugal pump).
–
Operation components (shut-off valves, drain valve).
Hereinafter are the descriptions of the operation of each single component.
PRESSURE GAUGE
The manometer indicates the reached steam pressure value. The value of the design pressure is shown in red on the graduated
scale.
The manometer is fitted onto a three-way valve allowing to carry out the following operations:
–
Communication between generator and pressure gauge (normal operating position).
–
Communication between pressure gauge and the outside (position needed to purge the siphon).
–
Communication between generator, pressure gauge and sample pressure gauge (position needed for pressure gauge
comparison).