General information
9
APPLIANCE DESCRIPTION
Systems
ECOVAPOR
are automatically-operated appliances for high pressure (12 bar) steam production from 350 to 3000 kg/h.
The horizontal combustion chamber is of the reverse flame type and the tube bundle is complete with helical turbulators.
The patented combustion system, with pre-mixing and flue gas recirculation, only for natural gas (CH4), allowing to obtain high
efficiency levels, low emissions and a thermal power modulation from 1 to 10, is integrated inside the front door and in the rear
smokebox.
The generator body is thermally insulated through a high-density mineral wool mattress protected by stainless steel panels to
minimise losses.
They use a single control panel where the whole electric wiring of the appliance merges, and including the touch-screen
operator's panel, the burner managing control unit, with display, the burner motor inverter, controls of several devices and an air-
conditioning system to ensure a temperature suitable to the devices.
The steam generating system
ECOVAPOR
has been designed for the installation inside closed heating plant rooms with an
ambient temperature below 50 °C; it rests on a support made of carbon steel section bars ensuring its stability.
They are equipped with water side inspection opening (flanged hatch).
STRUCTURE
FRONT VIEW
3
2
1
8 9
10 11
16
19
17
18
6
5
4
7
13
15
14
12
1
Door locking system
2
Front door
3
Pressure transducer
4
Pressure transducer
5
First safety level probe (minimum)
6
Maximum level probe
7
Capacitive probe with pre amplifier
8
Pressure gauge
9
Second safety level probe (minimum)
10
Front door
11
Front door
12
Pressure transducer
13
Pressure transducer
14
First safety level probe (minimum)
15
Maximum level probe
16
Capacitive probe with pre amplifier
17
Pressure gauge
18
Second safety level probe (minimum)
19
Front door
m
IMPORTANT
Drawing, legend and data refer to standard models
For specific models refer to the supplied accessory manual