background image

QD-ENG-40 REV.3

 

- 3 - 

 

INTRODUCTION:  

 

Ice Qube’s Thermal Management

  S

ystem, TMS, is designed to cool, dehumidify or heat the internal 

environment of modern electrical enclosures.  Ice Qube offers efficient and aesthetically appealing 
packages that can be mounted on top or on the side of your enclosure.  Our closed-loop circulation 
design protects your equipment from air-borne dust and contaminants which may hinder equipment 
operations, causing unnecessary down time.  Ice Qube is able to provide cooling capacities from 
1,000 to 27,000 BTU per hour - a wide range of cooling systems to satisfy many of your conditioning 
needs.  

 

BASIC OPERATION: 

 

The Ice Qube’s Thermal Management System, TMS, is actually a combination of three independent 
systems which function simultaneously to maintain environmentally friendly conditions for various 
types of electronic equipment enclosures.  These three thermal related systems are: the closed-loop 
cool air system; the warm air system; and the vapor-compression refrigeration system.   Please refer 
to Figure 1. 
 
The closed-loop cool air system circulates cold air from the Ice Qube TMS to the electronics 
enclosure.  This air returns to the Ice Qube system bringing with it unwanted heat and humidity from 
inside the enclosure.  Heat and humidity is then removed by a heat exchanger located within the Ice 
Qube TMS.  This heat exchanger is part of the vapor-compression refrigeration system.

 

 

At the heart of the vapor-compression refrigeration’s system is a quiet, energy efficient rotary 
compressor which circulates environmentally friendly NON-CFC refrigerant.  The main purpose of this 
compressor is to transfer heat laden refrigerant from the evaporator, located within the closed-loop 
cool air system, to a condenser, located in the warm air system.  In the warm air system, air is 
circulated from the ambient surrounding the enclosure, through a filter, and across the warm air 
system heat exchanger.  Here, heat from the enclosure is transferred from the warm air heat 
exchanger into the warm air stream and dissipated to the ambient. 

 

Figure 1:  Flow Diagram 

 
 
 

 
 
 
UNPACKING INSPECTION: 

Summary of Contents for IQ27000V

Page 1: ...s IQ27000V OPERATION AND INSTALLATION MANUAL IMPORTANT PLEASE READ this manual and follow the instructions for safe and satisfactory installation and operation of this system Keep this manual for futu...

Page 2: ...unit Page 4 Preparing the Enclosure Page 5 Operating the System Page 6 Programming the Controller Page 7 Figure 3 Digital Controller Page 7 Alarm Operation Page 9 Maintenance Page 10 Trouble Shooting...

Page 3: ...rm air system and the vapor compression refrigeration system Please refer to Figure 1 The closed loop cool air system circulates cold air from the Ice Qube TMS to the electronics enclosure This air re...

Page 4: ...reported to the carrier The freight carrier will provide instructions on filing a claim Ice Qube cannot accept responsibility for damages that occur during shipping PRE INSTALLATION TEST Before insta...

Page 5: ...erature if the room temperature is warmer than 70 F Inlet air temperature will be displayed on the programmable controller In areas of high humidity the temperature difference may be less than 10 degr...

Page 6: ...lied nuts and bolts Check to see if the power cable and all optional cables are in place Fasteners need to be tightened securely and the gasket material needs to be in place in order to maintain enclo...

Page 7: ...icates the heat relay has been energized and is providing power to the heater There is no time delay before heating begins When the temperature of the enclosure rises 7 degrees Fahrenheit above the se...

Page 8: ...ue The set alarm HI LED is on with the display indicating the high temperature alarm setpoint The alarm will activate at this temperature and will automatically reset at two degrees Fahrenheit one deg...

Page 9: ...the number of days that the alarm is set in one half day increments Note that the alarm is based on compressor run time Example 10 5 indicates the alarm will activate every ten and one half days or o...

Page 10: ...ernating E O C O display may indicate the sensor connector has become disconnected from the rear of the controller 7 Incorrect Voltage Supply A continual flashing value of the program version 3 1x x i...

Page 11: ...ay prevent water flow through the nipple To clean the debris from the pan use a clean absorbent cloth or shop vac Nipples may be cleaned using a inch tubing brush then flush with clean water Also insp...

Page 12: ...NO Is the power cord connected to the electrical supply YES NO Is the controller set point temperature above or below the enclosure temperature YES NO Is the evaporator cold air stream blower operati...

Page 13: ...QD ENG 40 REV 3 13 WIRING SCHEMATIC DIAGRAM 230 volt...

Page 14: ...QD ENG 40 REV 3 14 WIRING SCHEMATIC DIAGRAM 480volt...

Page 15: ...QD ENG 40 REV 3 15 SPECIFICATION DRAWING ONE...

Page 16: ...QD ENG 40 REV 3 16 SPECIFICATION DRAWING TWO All current documentation and cut out templates can also be found on our website at www iceqube com...

Page 17: ...OF TRADE OR OTHERWISE SPECIFICALLY EXCLUDING ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OR USE 1 The warranty and remedies for breach of warranty provided for in th...

Page 18: ...sity of in field service for such Product in its sole discretion Ice Qube will not assume any liability for any in field service not initiated by Ice Qube In no event shall Ice Qube be liable for any...

Reviews: