background image

QD-ENG-40 REV.3

 

- 10 - 

 

ALARM OPERATION: 

- continued -

 

 

2. 

The condenser temperature is above the condenser alarm setpoint

The alarm LED lights, the display flashes the condenser temperature, and the audible alarm 
sounds (if activated).  The condenser temperature must fall four degrees Fahrenheit (two degrees 
Celsius) before the alarm will reset.  

The above alarms can be manually reset by entering the 

PIN code into the system.    

 

3. 

The filter day timer has expired

The alarm LED lights, the display flashes showing “

FIL”

, the filter LED flashes with the display and 

the audible alarm sounds (if activated).  The filter alarm may be cleared by pressing “

4 Exit”. 

 

4. 

The power is turned off. 

The alarm LED lights, and the display flashes showing “OFF” indicating someone has manually 
interrupted power to the motors’ electrical circuits.  This alarm will be reset when the Por “ON” has 
been selected in the program menu. 

(Version 3.18 and later only)

  

       

 

5. 

Optional Alarm Output: 

Ice Qube also offers an optional alarm output that is provided through an alarm relay.  This option 
is a dry contact (no voltage) set of contacts that may be configured as: 
 

 

Normally Open    (X01 – close on alarm condition),  Black & White wires 

 

 

Normally Closed  (X02 – open on alarm condition),  Black & Red wires 

 

Normally Open and Normally Closed  (X03 – close on alarm condition),  

 

 

 

 

 

 

 

        Black, White & Red wires

 

6. 

Sensor Malfunctions

 

E-O  -  Evaporator sensor open 

 

E-C  -  Evaporator sensor shorted 

 

C-O  -  Condenser sensor open 

 

C-C  -  Condenser sensor shorted 

 

NOTE:  An alternating E-O … C-O display may indicate the sensor connector has become 

disconnected from the rear of the controller. 

 

7. 

Incorrect Voltage Supply

 

A continual flashing value of the program version (

“3.1x

” = x indicates current program version) on 

the display screen indicates the supply voltage is either too high or too low. 

 

 

 

 

MAINTENANCE: 

 

The Ice Qube air conditioning system is designed to provide many years of trouble-free operation with 
minimal amount of maintenance.  Primary maintenance consists of checking the condition of the 
ambient air filter and the condensate management system. 

 

1. 

Ambient Air Filters

:  It is recommended that the ambient air filters be inspected and cleaned 

regularly; frequency will depend upon ambient conditions.  To check the condition of the air 
filter, it is recommended to first remove electrical power from the Ice Qube system.  Next, 
locate the filter cover and filter, (location will vary by model).  Slide the filter from the filter rack 
through the end slot and clean by soaking in warm soapy water.  Rinse with clean water.  Use 
a shop-vac to remove excess water from the filter before returning it to the system.  Replace 
the filter if it is showing signs of deterioration.   

 

NOTE: If rain or wash down hoods have been installed, a filter would not have been 

supplied, therefore no filter maintenance is required.  However systems 
equipped with rain or wash down hoods will require regular condensing 
section maintenance by qualified personnel.  For systems equipped with 
filters, it is recommended to have a spare clean filter in stock in order to 
prevent prolonged cooling system downtime.  The dirty filter may be cleaned 
at a more convenient time. 

 
 

Summary of Contents for IQ27000V

Page 1: ...s IQ27000V OPERATION AND INSTALLATION MANUAL IMPORTANT PLEASE READ this manual and follow the instructions for safe and satisfactory installation and operation of this system Keep this manual for futu...

Page 2: ...unit Page 4 Preparing the Enclosure Page 5 Operating the System Page 6 Programming the Controller Page 7 Figure 3 Digital Controller Page 7 Alarm Operation Page 9 Maintenance Page 10 Trouble Shooting...

Page 3: ...rm air system and the vapor compression refrigeration system Please refer to Figure 1 The closed loop cool air system circulates cold air from the Ice Qube TMS to the electronics enclosure This air re...

Page 4: ...reported to the carrier The freight carrier will provide instructions on filing a claim Ice Qube cannot accept responsibility for damages that occur during shipping PRE INSTALLATION TEST Before insta...

Page 5: ...erature if the room temperature is warmer than 70 F Inlet air temperature will be displayed on the programmable controller In areas of high humidity the temperature difference may be less than 10 degr...

Page 6: ...lied nuts and bolts Check to see if the power cable and all optional cables are in place Fasteners need to be tightened securely and the gasket material needs to be in place in order to maintain enclo...

Page 7: ...icates the heat relay has been energized and is providing power to the heater There is no time delay before heating begins When the temperature of the enclosure rises 7 degrees Fahrenheit above the se...

Page 8: ...ue The set alarm HI LED is on with the display indicating the high temperature alarm setpoint The alarm will activate at this temperature and will automatically reset at two degrees Fahrenheit one deg...

Page 9: ...the number of days that the alarm is set in one half day increments Note that the alarm is based on compressor run time Example 10 5 indicates the alarm will activate every ten and one half days or o...

Page 10: ...ernating E O C O display may indicate the sensor connector has become disconnected from the rear of the controller 7 Incorrect Voltage Supply A continual flashing value of the program version 3 1x x i...

Page 11: ...ay prevent water flow through the nipple To clean the debris from the pan use a clean absorbent cloth or shop vac Nipples may be cleaned using a inch tubing brush then flush with clean water Also insp...

Page 12: ...NO Is the power cord connected to the electrical supply YES NO Is the controller set point temperature above or below the enclosure temperature YES NO Is the evaporator cold air stream blower operati...

Page 13: ...QD ENG 40 REV 3 13 WIRING SCHEMATIC DIAGRAM 230 volt...

Page 14: ...QD ENG 40 REV 3 14 WIRING SCHEMATIC DIAGRAM 480volt...

Page 15: ...QD ENG 40 REV 3 15 SPECIFICATION DRAWING ONE...

Page 16: ...QD ENG 40 REV 3 16 SPECIFICATION DRAWING TWO All current documentation and cut out templates can also be found on our website at www iceqube com...

Page 17: ...OF TRADE OR OTHERWISE SPECIFICALLY EXCLUDING ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OR USE 1 The warranty and remedies for breach of warranty provided for in th...

Page 18: ...sity of in field service for such Product in its sole discretion Ice Qube will not assume any liability for any in field service not initiated by Ice Qube In no event shall Ice Qube be liable for any...

Reviews: