QD-ENG-40 REV.3
- 10 -
ALARM OPERATION:
- continued -
2.
The condenser temperature is above the condenser alarm setpoint
:
The alarm LED lights, the display flashes the condenser temperature, and the audible alarm
sounds (if activated). The condenser temperature must fall four degrees Fahrenheit (two degrees
Celsius) before the alarm will reset.
The above alarms can be manually reset by entering the
PIN code into the system.
3.
The filter day timer has expired
:
The alarm LED lights, the display flashes showing “
FIL”
, the filter LED flashes with the display and
the audible alarm sounds (if activated). The filter alarm may be cleared by pressing “
4 Exit”.
4.
The power is turned off.
The alarm LED lights, and the display flashes showing “OFF” indicating someone has manually
interrupted power to the motors’ electrical circuits. This alarm will be reset when the Por “ON” has
been selected in the program menu.
(Version 3.18 and later only)
5.
Optional Alarm Output:
Ice Qube also offers an optional alarm output that is provided through an alarm relay. This option
is a dry contact (no voltage) set of contacts that may be configured as:
Normally Open (X01 – close on alarm condition), Black & White wires
Normally Closed (X02 – open on alarm condition), Black & Red wires
Normally Open and Normally Closed (X03 – close on alarm condition),
Black, White & Red wires
.
6.
Sensor Malfunctions
:
E-O - Evaporator sensor open
E-C - Evaporator sensor shorted
C-O - Condenser sensor open
C-C - Condenser sensor shorted
NOTE: An alternating E-O … C-O display may indicate the sensor connector has become
disconnected from the rear of the controller.
7.
Incorrect Voltage Supply
A continual flashing value of the program version (
“3.1x
” = x indicates current program version) on
the display screen indicates the supply voltage is either too high or too low.
MAINTENANCE:
The Ice Qube air conditioning system is designed to provide many years of trouble-free operation with
minimal amount of maintenance. Primary maintenance consists of checking the condition of the
ambient air filter and the condensate management system.
1.
Ambient Air Filters
: It is recommended that the ambient air filters be inspected and cleaned
regularly; frequency will depend upon ambient conditions. To check the condition of the air
filter, it is recommended to first remove electrical power from the Ice Qube system. Next,
locate the filter cover and filter, (location will vary by model). Slide the filter from the filter rack
through the end slot and clean by soaking in warm soapy water. Rinse with clean water. Use
a shop-vac to remove excess water from the filter before returning it to the system. Replace
the filter if it is showing signs of deterioration.
NOTE: If rain or wash down hoods have been installed, a filter would not have been
supplied, therefore no filter maintenance is required. However systems
equipped with rain or wash down hoods will require regular condensing
section maintenance by qualified personnel. For systems equipped with
filters, it is recommended to have a spare clean filter in stock in order to
prevent prolonged cooling system downtime. The dirty filter may be cleaned
at a more convenient time.