background image

Model VIP+

 

27 

Owner's Manual 

Cleanout and maintenance 

Grease duct is required by NFPA 96 and many local building codes to be inspected and cleaned (if necessary) at specific intervals.  VIP+ Grease 
Duct must be inspected and cleaned in accordance with  local requirements. It requires no additional internal maintenance.   *Canadian regulation 
requires that an access opening shall be provided on each section of horizontal duct for duct cleaning.  The access opening shall be minimum 505 
mm (20") by 505 mm(20").  Where the duct size is such that the opening is not possible, openings large enough to permit thorough cleaning shall be 
provided at least every 3.7 m (12ft). 
 
ICC recommends that grease containers connected to drainage points be emptied and washed out daily or more often, if necessary. If needed, the 
drain nipples should be checked and cleaned whenever the containers are emptied.  
 
Where  the  duct  is  installed  outside  the  building,  the  Galvalume  steel  outer  casing  must  be  primed  and  painted.  The  paint  surface  should  be 
maintained regularly to prevent possible deterioration of the casing surface. The use of stainless steel outer casing negates the need for painting. 

 

Creosote and Soot – Formation and Need for Removal  (For pizza oven and other solid fuel cooking devices) 
 
When  wood  is  burned  slowly,  it  produces  tar  and  organic  vapors  which  combines  with  expelled  moisture  to  form  creosote.  The  creosote  vapors 
condense in the relatively cool grease duct of a slow burning fire. As a result, creosote residue accumulates on the duct. If ignited, this creosote 
makes an extremely hot fire. For this reason, the duct should be inspected at least once every two months to determine if a creosote or soot buildup 
has  occurred.  Consult  local  code  and  officials  as  they  might  require  more  frequent  intervals.  If  creosote  or  soot  has  accumulated,  it  should  be 
removed to reduce risk of fire. 
 
A  licensed  or  qualified  grease  duct  cleaner  should  be  contacted  to  clean  the  duct.  Contact  local  building  or  fire  officials  about  restrictions  and 
installation  inspection  in  your  area.  Adequate  clearance  is  required  around  cleanouts  to  assure  accessibility  for  removal  of  caps  and  products 
accumulated within the grease duct. 
 

Access Door Section 

The  Access  door  section  (

Figure  42

 

and 

Figure 43

) is installed in line with 

the pipe to provide an inspection and 
cleaning  access  point.    It  doesn't 
require  specific  tools  since  the 
access  panels  (both  outside  casing 
and  flue)  are  secured  with  thumb 
screws.    The  Access  Door  section 
comes  pre-assembled  from  the 
factory. 
 
The  flue  panels  can  be  accessed 
after  removal  of  the  outside  casing 
door and insulation pad (for insulated 
Grease  Ducts).    To  remove  the 
outside  panel,  unscrew  and  remove 
all the thumb screws. 
 
The inside access door is made of 2 
panels.    The  outside  flue  panel  is 
screwed into a smaller panel that fits 
inside the flue.  To remove, unscrew 
all  thumb  screws.  The  2  bottom 
middle  screws  can  be  loosen  but 
can't be removed.  This allows the 2 
plates  to  remain  joined  together  but 
gives  enough  clearance  to  pull  the 
inside panel out of the flue opening. 
 
The  Access  Door  is  attached  and 
sealed  to  other  pipe  sections  in  the 
same  manner  as  described  in 

Chimney Joint Connection

 Section.

 

 

 

Figure 42 

Figure 43 

Fixed 

Wing Screws 

Outside Casing 

Panel 

Inside Panels 

Insulation Pad 

Summary of Contents for VIP+ Air Insulated

Page 1: ...he ICC Model VIP venting system until you have carefully read the appliance and vent system installation instructions Use only ICC Model VIP components Failure to do so will void the certification and...

Page 2: ...0 Base Support 10 Wall Support 11 Wall Guide 12 Floor Guide 12 Support Methods and System Design Limits 13 Rigid Structural Brace Specifications 14 Elbows and Offsets 14 Guy Wire 15 Roof and Floor Pen...

Page 3: ...id oil or solid fuel fired appliances Also complies with operation less than one hour at temperatures not exceeding 760 C 1400 F and brief operation maximum 10 minutes at temperatures not exceeding 92...

Page 4: ...6 to 24 6 7 Ventilated Firestop See Roof and Floor Penetrations section for details Part Numbers The following section describes how part number are defined for most of the major VIP products Please r...

Page 5: ...for flue and casing 26 ga min up to 16 and 24 ga min 18 and over C Galvalume Alu Zinc Available for casing only 26 ga min up to 16 and 24 ga min 18 and over Standard materials only for other options...

Page 6: ...ing the vent before closing up any enclosed areas Planning your Installation Prior to starting your installation we suggest you take the following into consideration 1 Check the appliance manufacturer...

Page 7: ...amix TC 2280 F 1250 C Outer Joints Any Silicone Sealant with a min rating of 400 F 400 F Outer Joints Any Silicone Sealant with a min rating of 400 F 400 F Fortafix Ceramix TC cure time Air dry for 24...

Page 8: ...to chimney label for flue gases direction Step 3 Assemble the flue locking band and secure by tightening the bolt Do not remove the excess of sealant Step 4 Install locking band insulation strip arou...

Page 9: ...nd Bead of Fortafix Ceramix TC just above the formed bead when chimneys are joined together before interior locking band assembly Step 4 Assemble the interior locking band around the flue and secure b...

Page 10: ...7 effective length that is welded to a steel plate The chimney section has female and male ends forming just like any standard length It can be connected to any other piece of piping with proper locki...

Page 11: ...bands and sealant see Chimney Joint Connection Section for specific instructions It is supplied with both an Interior Locking Band a special External Finishing Band top female side and an Insulation S...

Page 12: ...with a minimum of 3 anchors on each side by others See Table 7 for Maximum Vertical Spacing between 2 Supports or Guides MVS Figure 12 Figure 13 Floor Guide The Floor Guide is mainly used as a chimney...

Page 13: ...plication Table 6 Maximum Supported Chimney Height and Support Method MCH Support Method VIP Chimney Model MCH feet VIP AIR Insulated VIP 1 Fiber VIP 2 Fiber VIP 4 Fiber Base Support 6 to 24 51 39 30...

Page 14: ...burning appliances Chimneys for combination fuel heating appliances that are capable of burning solid fuel or are convertible to solid fuel are limited to 30 slope even if the current choice of fuel i...

Page 15: ...The Guy Wire Band is made to hook up 3 guy wire by others at 120 apart or to be secured with Rigid Roof Brace by others The cables are secured to the roof by mean of tensioners by others and anchors b...

Page 16: ...ss than one hour at temperatures not exceeding 760 C 1400 F and brief operation maximum 10 minutes at temperatures not exceeding 906 C 1700 F An Insulated Radiation Shield must be used where a chimney...

Page 17: ...of combustible material It is designed to be installed on a flat roof or roof curb 8 to 16 high The roof framing dimensions are presented in Table 8 in the previous Section 1 The Radiation Shield is i...

Page 18: ...primarily used for Engines or High Temperature Applications where a chimney section passes through a roof made of combustible material It is designed to be installed on a flat roof or roof curb 4 to 1...

Page 19: ...to 6 inches water column can effectively use the Expansion Length Table 9 Allowable lengths for 1 4 thermal expansion T Gas T Surroundings T F Length between fixed points 200 12 6 300 8 4 400 6 3 500...

Page 20: ...oint Connection Section 4 Bellow Joint is used for axial movements and vibration only and must be accurately supported and guided This part has limited lateral movement Lateral offsets and parallel mi...

Page 21: ...asket between the two flanges and secure with the supplied bolts Use a star tightening pattern of the bolts for better stability Re tighten the compression band bolt if necessary 6 Install Insulation...

Page 22: ...all precautions for cleaning sealed surfaces and use proper sealant as described in the Sealant Application Chart section see Table 4 It can be used in horizontal or vertical runs and also between el...

Page 23: ...Model VIP 23 Owner s Manual Figure 36...

Page 24: ...Model VIP 24 Owner s Manual Figure 37...

Page 25: ...ending from the penetration through any concealed spaces to or through the roof so as to maintain the integrity of the fire separations required by the applicable building code The enclosure shall be...

Page 26: ...be used to integrate automatic cleaning or fire suppression devices by others to a Grease Duct installation The Nozzle Length comes with a 3 4 NPT nipple both ends that can be connected to an automat...

Page 27: ...sote makes an extremely hot fire For this reason the duct should be inspected at least once every two months to determine if a creosote or soot buildup has occurred Consult local code and officials as...

Page 28: ...m position 2 T2 Grease Tee Figure 46 has inverted female and male ends and covers mostly horizontal grease dam configurations Refer to Figure 47 for dam position When ordering you GreaseTee please spe...

Page 29: ...Fan Adapter Roof Curb by others Exhaust Hoods by others Grease Duct Wye Tee Cap Grease Tee T2 P3 Dam Position Chimney Sections 90 Tee Standard TR Horizontal Band Base Support Base Support Supporting...

Page 30: ...vanized or steel surfaces must be protected at all times by a minimum of one base coat of primer and one finish coat of heat resistant and corrosion resistant paint Stainless steel surfaces need not b...

Reviews: