background image

Model VIP+

 

14 

Owner's Manual 

Rigid Structural Brace Specifications 

When necessary a Support Assembly must be secured to the building with a rigid structural framework.  Satisfactory performance and service life of 
VIP+ Chimney Systems requires the product be rigidly braced and supported.  Every installation presents unique support and bracing requirements 
and the following guidelines will provide minimum acceptable sizes for the mechanical hardware supplied by others.   
 

 

Figure 17

 

 

Figure 18

 

 

Elbows and Offsets 

 

Elbows are used for changes in direction in horizontal or vertical portions of a chimney system.  

 

Elbows are used in combination to make up different angles in horizontal and vertical breechings of the chimney. 

 

Special  care  should  be  exercised  in  designing  the  bracing  for  elbows  because  elbows  can  only  take  limited  forces  due  to  any  bending 
moments 

 

Except  where  absolutely  necessary,  sloped  or  horizontal  offsets  in  the  vertical  portion  of  a  chimney  above  the  breeching  should  be 
avoided.  

 

Sloped offsets require more expansion joints and secure bracing above and below elbows.  

 

Structural parts such as posts or beams may also be needed to hold chimney supports in position.  

 

There is no limit on the angle or slope of an offset for gas or liquid fuel burning appliances 

 

Chimneys for combination fuel heating appliances that are capable of burning solid fuel or are convertible to solid fuel are limited to 30º 
slope even if the current choice of fuel is gas or oil.  

 

The maximum length of offset, if one is necessary, is determined by strength considerations. The maximum dimension between supports 
(Base Supports or Wall Supports), given as the “

MHS

” dimension in the 

Support Methods and System Design Limits (Table 7)

 section 

of these instructions, is applicable to all horizontal and sloped orientations. (See 

Figure 20

 

To assure proper guidance of expansion joints and to prevent unnecessary joint bending, use an adequate number of supports at closer 
intervals.  

 

With generator set or turbine exhaust use Bellows Expansion Joint below each support in offset runs. For boiler exhaust use an Expansion 
Length. 

 

The ends of any sloped or horizontal offset must be anchored to prevent overstressing elbows and to assure proper operation of expansion 
joints. 

 

With  frequent  re-support,  there  is  no  structural  or  operational  limit  to  the  length  of  horizontal  or  sloped  portions  of  a  VIP+  Chimney, 
providing the system meets the capacity, pressure drop or available draft requirements of the appliance or equipment. 

 

The carrying capacity of the VIP+ supports and their structure attachments must consider the weight of the offset plus whatever vertical 
pipe is carried by that support.  See 

Table 6

 for height limit of VIP+ supports (

MCH

). 

Summary of Contents for VIP+ Air Insulated

Page 1: ...he ICC Model VIP venting system until you have carefully read the appliance and vent system installation instructions Use only ICC Model VIP components Failure to do so will void the certification and...

Page 2: ...0 Base Support 10 Wall Support 11 Wall Guide 12 Floor Guide 12 Support Methods and System Design Limits 13 Rigid Structural Brace Specifications 14 Elbows and Offsets 14 Guy Wire 15 Roof and Floor Pen...

Page 3: ...id oil or solid fuel fired appliances Also complies with operation less than one hour at temperatures not exceeding 760 C 1400 F and brief operation maximum 10 minutes at temperatures not exceeding 92...

Page 4: ...6 to 24 6 7 Ventilated Firestop See Roof and Floor Penetrations section for details Part Numbers The following section describes how part number are defined for most of the major VIP products Please r...

Page 5: ...for flue and casing 26 ga min up to 16 and 24 ga min 18 and over C Galvalume Alu Zinc Available for casing only 26 ga min up to 16 and 24 ga min 18 and over Standard materials only for other options...

Page 6: ...ing the vent before closing up any enclosed areas Planning your Installation Prior to starting your installation we suggest you take the following into consideration 1 Check the appliance manufacturer...

Page 7: ...amix TC 2280 F 1250 C Outer Joints Any Silicone Sealant with a min rating of 400 F 400 F Outer Joints Any Silicone Sealant with a min rating of 400 F 400 F Fortafix Ceramix TC cure time Air dry for 24...

Page 8: ...to chimney label for flue gases direction Step 3 Assemble the flue locking band and secure by tightening the bolt Do not remove the excess of sealant Step 4 Install locking band insulation strip arou...

Page 9: ...nd Bead of Fortafix Ceramix TC just above the formed bead when chimneys are joined together before interior locking band assembly Step 4 Assemble the interior locking band around the flue and secure b...

Page 10: ...7 effective length that is welded to a steel plate The chimney section has female and male ends forming just like any standard length It can be connected to any other piece of piping with proper locki...

Page 11: ...bands and sealant see Chimney Joint Connection Section for specific instructions It is supplied with both an Interior Locking Band a special External Finishing Band top female side and an Insulation S...

Page 12: ...with a minimum of 3 anchors on each side by others See Table 7 for Maximum Vertical Spacing between 2 Supports or Guides MVS Figure 12 Figure 13 Floor Guide The Floor Guide is mainly used as a chimney...

Page 13: ...plication Table 6 Maximum Supported Chimney Height and Support Method MCH Support Method VIP Chimney Model MCH feet VIP AIR Insulated VIP 1 Fiber VIP 2 Fiber VIP 4 Fiber Base Support 6 to 24 51 39 30...

Page 14: ...burning appliances Chimneys for combination fuel heating appliances that are capable of burning solid fuel or are convertible to solid fuel are limited to 30 slope even if the current choice of fuel i...

Page 15: ...The Guy Wire Band is made to hook up 3 guy wire by others at 120 apart or to be secured with Rigid Roof Brace by others The cables are secured to the roof by mean of tensioners by others and anchors b...

Page 16: ...ss than one hour at temperatures not exceeding 760 C 1400 F and brief operation maximum 10 minutes at temperatures not exceeding 906 C 1700 F An Insulated Radiation Shield must be used where a chimney...

Page 17: ...of combustible material It is designed to be installed on a flat roof or roof curb 8 to 16 high The roof framing dimensions are presented in Table 8 in the previous Section 1 The Radiation Shield is i...

Page 18: ...primarily used for Engines or High Temperature Applications where a chimney section passes through a roof made of combustible material It is designed to be installed on a flat roof or roof curb 4 to 1...

Page 19: ...to 6 inches water column can effectively use the Expansion Length Table 9 Allowable lengths for 1 4 thermal expansion T Gas T Surroundings T F Length between fixed points 200 12 6 300 8 4 400 6 3 500...

Page 20: ...oint Connection Section 4 Bellow Joint is used for axial movements and vibration only and must be accurately supported and guided This part has limited lateral movement Lateral offsets and parallel mi...

Page 21: ...asket between the two flanges and secure with the supplied bolts Use a star tightening pattern of the bolts for better stability Re tighten the compression band bolt if necessary 6 Install Insulation...

Page 22: ...all precautions for cleaning sealed surfaces and use proper sealant as described in the Sealant Application Chart section see Table 4 It can be used in horizontal or vertical runs and also between el...

Page 23: ...Model VIP 23 Owner s Manual Figure 36...

Page 24: ...Model VIP 24 Owner s Manual Figure 37...

Page 25: ...ending from the penetration through any concealed spaces to or through the roof so as to maintain the integrity of the fire separations required by the applicable building code The enclosure shall be...

Page 26: ...be used to integrate automatic cleaning or fire suppression devices by others to a Grease Duct installation The Nozzle Length comes with a 3 4 NPT nipple both ends that can be connected to an automat...

Page 27: ...sote makes an extremely hot fire For this reason the duct should be inspected at least once every two months to determine if a creosote or soot buildup has occurred Consult local code and officials as...

Page 28: ...m position 2 T2 Grease Tee Figure 46 has inverted female and male ends and covers mostly horizontal grease dam configurations Refer to Figure 47 for dam position When ordering you GreaseTee please spe...

Page 29: ...Fan Adapter Roof Curb by others Exhaust Hoods by others Grease Duct Wye Tee Cap Grease Tee T2 P3 Dam Position Chimney Sections 90 Tee Standard TR Horizontal Band Base Support Base Support Supporting...

Page 30: ...vanized or steel surfaces must be protected at all times by a minimum of one base coat of primer and one finish coat of heat resistant and corrosion resistant paint Stainless steel surfaces need not b...

Reviews: