23
BACnet / Electric Water Heaters
BACNET / ELECTRIC WATER HEATERS
Figure 35. Custom and Gold Xi™ Series Electric Water Heaters (Virtual BACnet device via ICC Gateway)
PRODUCT DESCRIPTION
The Mirius is a multiprotocol RS-485 to RS-485 gateway. The ETH-1000 is an Ethernet to RS-485 multiprotocol gateway. These
products supports native BACnet, connecting directly to IP or the MS/TP LAN using baud rates of 4800, 9600, 19200, 38400, 57600,
76800, and 115200. As shipped the devices are configured as a BACnet Server.
All electronic controls provide communications via propriety protocol with the ICC Gateway. The Mirius supports BACnet MS/TP
communications and the ETH-1000 supports BACnet IP to access data available at the display plus control of a limited number of
points such as Operating Setpoint.
PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT (PICS)
BACnet Standardized Device Profile (Annex L):
BACnet Application Specific Controller (B-ASC)
BACnet Interoperability
Table 15. BACnet Interoperability Building Blocks Supported (Annex K):
Data Sharing - ReadProperty-A (DS-RP-A)
Data Sharing - ReadProperty-B (DS-RP-B)
Data Sharing - ReadPropertyMultiple-B (DS-RPM-B)
Data Sharing - WriteProperty-A (DS-WP-A)
Data Sharing - WriteProperty-B (DS-WP-B)
Data Sharing - WritePropertyMultiple-B (DS-WPM-B)
Data Sharing – COV-B (DS-COV-B) (BACnet/IP only)
Device Management-Dynamic Device Binding-A (DM-DDB-A)
Device Management-Dynamic Device Binding-B (DM-DDB-B)
Device Management-Dynamic Object Binding-B (DM-DOB-B)