BACnet / Boilers
Table 32. BACnet/Boiler Device Object
Property Name
ID
BACnet Data Type
RW
Initial Value
(Mirius)
Initial Value
(ETH-1000)
System_Status
112
R
Operational
Operational
Vendor_Name
121
R
ICC, Inc.
ICC, Inc.
Vendor_Identifier
120
R
242
242
Model_Name
70
R
Mirius
ETH-1000
Firmware_Revision
44
Character String
R
V3.300
V4.002
Application_Software_Version
12
R
V3.300
V4.002
Protocol_Version
98
R
1
Protocol_Revision
139
R
2
Protocol_Services_Supported
97
R
See PICS
Protocol_Object_Types_Supported
96
R
AI, AO, AV, BI,
BO, BV, MSI,
MSO, MSV
AI, AO, AV, BI,
BO, BV, MSI,
MSO, MSV
Object_List
76
R
See Table
See Table
Max_APDU_Length_Accepted
62
R
480
1444
Segmentation_Supported
107
R
3
3
APDU_Timeout
10
RW
1000ms
1000ms
Number_Of_APDU_Retries
73
R
3
3
Max_Master
64
RW
127
Unsupported
Device_Address_Binding
30
R
{}
{}
Local_Date
56
R
Unsupported
Unsupported
Local_Time
57
R
Unsupported
Unsupported
Boiler Device Object Min/Max Values
• Not all models support all registers. Also parameter names may be different than shown here on some models.
• This table may be subject to change in the future.
• Adjustable objects are in
bold
and indicated by “W” (writable).
Table 33. BACnet/Boiler Object List
BACnet
Object Name
(Description)
BACnet
Object
Type/Inst.
BACnet
Object
Property
R/W
Units
Min
Value
(if W)
Max
Value
(if W)
Outlet Sensor
Analog Input 1
Present_Value
R
ºC
Inlet Sensor
Analog Input 2
Present_Value
R
ºC
Tank Sensor
Analog Input 3
Present_Value
R
ºC
Burner 1 Rate %
Analog Input 4
Present_Value
R
%
Burner 2 Rate %
Analog Input 5
Present_Value
R
%
Burner 3 Rate %
Analog Input 6
Present_Value
R
%
Burner 4 Rate %
Analog Input 7
Present_Value
R
%
Master FireRate%
Analog Input 8
Present_Value
R
%
Slave 1 State
Analog Input 9
Present_Value
R
Number
(See
Slave 2 State
Analog Input 10
Present_Value
R
Slave 3 State
Analog Input 11
Present_Value
R
Slave 4 State
Analog Input 12
Present_Value
R
Number (See
Access Status
(Register Access Status)
Analog Input 13
Present_Value
R
Number (See
)
Lockout Code
(Lockout i.e., fault and hold code)
Analog Input 14
Present_Value
R