![ICC Mirius Installation Instructions Manual Download Page 50](http://html1.mh-extra.com/html/icc/mirius/mirius_installation-instructions-manual_3359219050.webp)
50
Modbus / Electric Water Heaters
Table 43. ModBus / Electric Water Heaters Register List
Register Name
(Description)
Register
Type
R/W
Units/Format
Min Value
(if W)
Max Value
(if W)
Differential Bank
3
Holding Register 209
R/W
ºC x 512
(ºF)
.6
(1)
11.1
(20)
Differential lBank
4
Holding Register 210
R/W
ºC x 512
(ºF)
.6
(1)
11.1
(20)
Differential Bank
5
Holding Register 211
R/W
ºC x 512
(ºF)
.6
(1)
11.1
(20)
CCB Control State
Input Register 1040
R
See
EMS Mode-Status
Holding Register 90
R/W
See
Fault Code
Input Register 1041
R
See
Alert Code
Input Register 1042
R
See
Number of Banks in Heater
Input Register 201
R
Number of Banks Commanded On
Input Register 213
R
Bank 1 Status
Input Status 3873
R
0=Off
1=On
Bank 2 Status
Input Status 3874
R
0=Off
1=On
Bank 3 Status
Input Status 3875
R
0=Off
1=On
Bank 4 Status
Input Status 3876
R
0=Off
1=On
Bank 5 Status
Input Status 3877
R
0=Off
1=On
Element Status
Input Register 219
R
Bit 0=Element 1
Bit 1=Element 2
.
.
.
Bit 14=Element 14
Tank Full (LWCO
Input Status 150
R
0=Open Switch
1=Closed Switch
AC Input 1 T’stat
Input Status 3428
R
0=Open
1=Closed
AC Input 2 T’stat
Input Status 3429
R
0=Open
1=Closed
Alarm Condition
Input Status 3441
R
0=Open
1=Closed
Alarm Relay Status
Input Status 3443
R
0=Open
1=Closed
Safety Relay Feedback
Input Status 147
R
0=Open
1=Closed
Temperature Probe Open
Input Status 65
R
0=False
1=True
Temperature Probe Short
Input Status 66
R
0=False
1=True
Temperature Probe ECO Status
Input Status 156
R
0=Open
1=Closed
Number of Cycles
2
Input Registers 1000 - 1001
R
Elapsed Time
2
Input Registers 1002 - 1003
R
Hours x 100
Elapsed Days
3
Input Register 1004
Days
Elapsed Hours
3
Input Register 1005
Hours
Heating Time
2
Input Registers 1006 - 1007
Hours x 100
Heating Days
3
Input Register 1008
R
Days
1. Data is Version (upper 8 bits) and Revision (lower 8 bits).
2. Data stored in two 16 bit registers “Big Endian” (Higher order bits in lower register number)
3. Hours and Days used together derived from Time (hours x 100) i.e. Elapsed Time of 13612.24 hours in “Days” and “Hours” = 567
days, 4 hours.
Summary of Contents for Mirius
Page 54: ...54 NOTES...
Page 55: ...55 NOTES...