27
The default timeout time in all cases is 0, which disables network timeout
handling. When nonzero, timeout processing does not begin until after a valid
network packet has been received by the unit on that port.
When the timeout time is nonzero and a communication interruption is
detected, the
timeout enable
selections for each point are inspected. Those
points that are found to have their timeout enable selections set to “enabled”
will then have their configured
timeout values
automatically written to their
assigned “source port” objects. This mechanism provides for a flexible set of
device failsafe conditions to be established on a point-by-point basis.
12.3
Point Configuration
As mentioned in section 1, the Network Gateway Series concept revolves
around a central “point database”, containing the value and access
characteristics for each network. With respect to the Network Gateway Series,
a “point” is simply an object that defines some sort of network access, mapping
and configuration data, as well as a single “value” attribute that can be read
from or written to by various communication ports or protocols.
The only restriction placed on this “central clearinghouse” concept is that only
one port can autonomously update the point’s value, “mirroring” its designated
object for other protocols to access. What this means is that although any
protocol can read from or write to a point’s internal value, most of the time that
point’s value will simply be mirroring a remote data object that resides on one of
the gateway’s subnets. The selection of what a specific point is to mirror is
performed via its “source port” selection.
For example, a point may be configured to contain Toshiba ASD parameter
mapping and Modbus master ID and register mapping information. However,
because both of these protocols act as “master” protocols, only one of them
can be allowed to continuously update the point’s value. If both master
protocols could simultaneously update the point’s internal value, it would
erratically alternate back and forth between the values designated by the
Toshiba parameter and Modbus register objects. Any “slave” protocol (Modbus
RTU slave, Modbus Plus MSTR reads & writes, etc.) can read from or write to a
point at any time, but only the protocol designated by the point’s “source port”
assignment will autonomously update the point’s value independent of any
other protocol traffic.
The “source port” designation also determines where a new point value will be
written to when a “slave” protocol writes a new value to the point. For example,
if the Modbus Plus connection is used to write new data that changes the value
of a point, how do we know where this new value will exit the gateway to arrive
at its final destination? The answer is that any new point values written by
“slave” protocols will generate “write” transactions only on the “source port”.
Summary of Contents for MBP-100
Page 8: ...7 2 Mechanical Diagrams 2 1 Enclosure Figure 1 Enclosure Dimensions units are inches...
Page 9: ...8 2 2 Mounting Clip Figure 2 Mounting Clip Dimensions units are inches...
Page 11: ...10 ASD Link LEDs Data Write LEDs ASD 2 ASD 3 ASD 1 Figure 5 Top View...
Page 33: ...32 Figure 12 HyperTerminal Properties Settings...