33
10.4
Supported Subpoints
The interface contains a predefined set of FLN subpoints used for configuring,
controlling and monitoring the drive (refer to Table 5).
Table 5: Supported Subpoints
Point
#
Point
Type
Subpoint
Name
Factory
Default
Units
Slope Intercept
On
Text
Off
Text
01 LAO
ADDRESS
99
–
1
0
–
–
02 LAO APPLICATION 2736 –
1
0
–
–
03 LAI OUTPUT
FREQ
0
HZ 0.01
0
–
–
04 LAI LOAD
CURRENT
0
PCT 0.01
0
–
–
05 LAI OUTPUT
VOLT
0
PCT 0.01
0
–
–
06 LAI INPUT
POWER
0
KW 0.01
0
–
–
07 LAI
KWH
0
KWH 0.01
0
–
–
08 LAI
RR
INPUT
0
PCT 0.01
0
–
–
09 LAI VI.II
INPUT
0
PCT 0.01
0
–
–
10 LAI FAULT
CODE
0
–
1
0
–
–
11
LAI
COMM CFG 5
0
–
1
0
–
–
12
LAI
COMM CFG 6
0
–
1
0
–
–
13 LDI
RUN.STOP
0
–
1
0
RUN STOP
14 LDI
FWD.REV
0
–
1
0
REV FWD
15 LDI FAULT
STATUS
0
–
1
0
FAULT NORM
16 LDI F
TERMINAL
0
–
1
0
ON
OFF
17 LDI R
TERMINAL
0
–
1
0
ON
OFF
18 LDI ST
TERMINAL
0
–
1
0
ON
OFF
19 LDI RES
TERMINAL
0
–
1
0
ON
OFF
20 LAO OVRD
TIME
1
HRS
1
0
–
–
21 LDI S1
TERMINAL
OFF
–
1
0
ON
OFF
22 LDI S2
TERMINAL
OFF
–
1
0
ON
OFF
23 LDI S3
TERMINAL
OFF
–
1
0
ON
OFF
24 LDI S4
TERMINAL
OFF
–
1
0
ON
OFF
25 LDI
OUT1
OFF
–
1
0
ON
OFF
26 LDI
OUT2
OFF
–
1
0
ON
OFF
27 LDI
FL
OFF
–
1
0
ON
OFF
28 LAO
FREQ
CMD
0
HZ 0.01
0
–
–