CAUTION:
To reduce the risk of electric shock or energy hazards:
v
This equipment must be installed by trained service personnel in a
restricted-access location, as defined by teh NEC and IEC 60950, The
Standard for Safety of Information Technology Equipment.
v
Connect the equipment to a reliably grounded, safety extra low voltage
(SELV) source. An SELV source is a secondary circuit that is designed so
that normal and single fault conditions do not cause the voltages to exceed
a safe level (60 V direct current).
v
The branch circuit overcurrent protection must be rated per the following
table.
v
Use copper wire conductor only, not exceeding 3 m (9.8 ft.) in length and
sized according to the following table.
v
Torque the wiring-terminal screws to the values in the following table.
v
Incorporate a readily available approved and rated disconnect device in the
field wiring.
(C033)
Table 1. Electrical connections
Circuit breaker rating
Minimum: 20 amps
Maximum: 20 amps
Wire size
16 AWG (IBM part number 90Y3538 DC
power cable from PDP output to server input)
1.31 mm2
Wiring terminal screw torque
v
inch-pounds (IBM part number, 90Y3538,
provided with connector, both ends)
v
newton-meters (Nm)
Safety
ix
Summary of Contents for RackSwitch G8000
Page 1: ...IBM System Networking RackSwitch G8000 Installation Guide...
Page 2: ......
Page 3: ...IBM System Networking RackSwitch G8000 Installation Guide...
Page 14: ...xii IBM System Networking RackSwitch G8000 Installation Guide...
Page 52: ...36 IBM System Networking RackSwitch G8000 Installation Guide...
Page 66: ...50 IBM System Networking RackSwitch G8000 Installation Guide...
Page 68: ...52 IBM System Networking RackSwitch G8000 Installation Guide...
Page 82: ...66 IBM System Networking RackSwitch G8000 Installation Guide...
Page 85: ......
Page 86: ...Part Number 00AY391 Printed in USA 1P P N 00AY391...