your use of local or remote power controls. When you set the switch to
local, the local power on/local force power off switch controls power for
the storage system. You can access this switch by opening the rear cover of
the storage system. When the local/remote switch is set to remote, the
power for the storage system is controlled by remote power control
settings that are entered in the DS8000 Storage Management GUI or DS
Service GUI.
Planning requirements:
None.
Local power on/local force power off switch
(Available on base frames) The local power on/local force power off switch
initiates a storage system power-on sequence or a storage system force
power off sequence. This switch is applicable only when the local/remote
switch is set to local. You can access this switch by opening the rear cover
of the storage system.
Planning requirements:
None.
DC-UPS circuit breaker switches
Each DC-UPS provides a circuit breaker switch which can be used to
remove connection to input line cord and output power of that DC-UPS. If
both DC-UPS circuit breakers are switched off all power is removed from
the rack immediately.
Attention:
These switches are to be used only in specific service actions
or in case of emergency. Switching both DC-UPS circuit breakers off in a
rack can result in loss of data.
The following power controls can be configured by a technical service
representative. You can also use the following power controls through the DS8000
Storage Management GUI (running on the management console):
Local power control mode
(Visible in the DS8000 Storage Management GUI) You cannot change this
setting in the DS8000 Storage Management GUI. This mode is enabled
when the local/remote switch that is on the storage system is in the local
position. When this setting is used, the local power on/local force
power-off switch that is on the storage system controls the power.
Planning requirements:
None.
Power outlet requirements
Plan for the required power outlets for the installation of your storage system.
The following power outlets are required:
v
Two independent power outlets for the two power cords that are needed by
each model.
Important:
To eliminate a single point of failure, independent power feeds to
each DS8000 power supply are required. At least one of the feeds should have
power conditioning to ensure an acceptable level of power quality as specified
in standards such as ANSI C84.1 and EN 50160. Further, each power source
must have its own wall circuit breaker.
156
DS8880 Introduction and Planning Guide
Summary of Contents for DS8880 Series
Page 1: ...IBM DS8880 Version 8 Release 5 Introduction and Planning Guide GC27 8525 16 IBM...
Page 12: ...xii DS8880 Introduction and Planning Guide...
Page 52: ...40 DS8880 Introduction and Planning Guide...
Page 68: ...56 DS8880 Introduction and Planning Guide...
Page 138: ...126 DS8880 Introduction and Planning Guide...
Page 184: ...172 DS8880 Introduction and Planning Guide...
Page 190: ...178 DS8880 Introduction and Planning Guide...
Page 194: ...182 DS8880 Introduction and Planning Guide...
Page 200: ...188 DS8880 Introduction and Planning Guide...
Page 206: ...194 DS8880 Introduction and Planning Guide...
Page 208: ...196 DS8880 Introduction and Planning Guide...
Page 216: ...204 DS8880 Introduction and Planning Guide...
Page 220: ...208 DS8880 Introduction and Planning Guide...
Page 222: ...210 DS8880 Introduction and Planning Guide...
Page 243: ......
Page 244: ...IBM Printed in USA GC27 8525 16...