Particulate contamination
Attention:
Airborne particulates (including metal flakes or particles) and reactive
gases acting alone or in combination with other environmental factors such as
humidity or temperature might pose a risk to the server that is described in this
document. Risks that are posed by the presence of excessive particulate levels or
concentrations of harmful gases include damage that might cause the server to
malfunction or cease functioning altogether. This specification sets forth limits for
particulates and gases that are intended to avoid such damage. The limits must not
be viewed or used as definitive limits, because numerous other factors, such as
temperature or moisture content of the air, can influence the impact of particulates
or environmental corrosives and gaseous contaminant transfer. In the absence of
specific limits that are set forth in this document, you must implement practices that
maintain particulate and gas levels that are consistent with the protection of human
health and safety. If IBM determines that the levels of particulates or gases in your
environment have caused damage to the server, IBM may condition provision of
repair or replacement of servers or parts on implementation of appropriate remedial
measures to mitigate such environmental contamination. Implementation of such
remedial measures is a customer responsibility.
Table 10. Limits for particulates and gases
Contaminant
Limits
Particulate
v
The room air must be continuously filtered with 40% atmospheric dust
spot efficiency (MERV 9) according to ASHRAE Standard 52.2
1
.
v
Air that enters a data center must be filtered to 99.97% efficiency or
greater, using high-efficiency particulate air (HEPA) filters that meet
MIL-STD-282.
v
The deliquescent relative humidity of the particulate contamination
must be more than 60%
2
.
v
The room must be free of conductive contamination such as zinc
whiskers.
Gaseous
v
Copper: Class G1 as per ANSI/ISA 71.04-1985
3
v
Silver: Corrosion rate of less than 300 Å in 30 days
Appendix B. Notices
235
Summary of Contents for 436854u - System x3200 M2 5U Mini Tower...
Page 1: ...System x3200 M2 Types 4367 and 4368 Problem Determination and Service Guide...
Page 2: ......
Page 3: ...System x3200 M2 Types 4367 and 4368 Problem Determination and Service Guide...
Page 32: ...14 System x3200 M2 Types 4367 and 4368 Problem Determination and Service Guide...
Page 50: ...32 System x3200 M2 Types 4367 and 4368 Problem Determination and Service Guide...
Page 64: ...46 System x3200 M2 Types 4367 and 4368 Problem Determination and Service Guide...
Page 138: ...120 System x3200 M2 Types 4367 and 4368 Problem Determination and Service Guide...
Page 258: ...240 System x3200 M2 Types 4367 and 4368 Problem Determination and Service Guide...
Page 265: ......
Page 266: ...Part Number 49Y0163 Printed in USA 1P P N 49Y0163...