14
3:
C
ONFIGURATION
Detmining On Battery Runtime
The battery pack charges when connected to an uninterruptible power supply. Refer to the battery runtime tables for corresponding
recharge times. Do not expect full battery run capability during the initial charge period.
Battery Runtime Tables
Note:
The recharge time is the approximate time it takes to get to 90% capacity from a complete discharge at a 50% load.
5000XHV model:
Number of Battery Packs
Load
(W)
Internal
+1 +2 +4
50 6:49 18:03 31:32 59:56
100 4:50 12:51 22:29 42:46
200 3:00 8:03 14:06
26:50
300 2:09 5:47 10:10
19:22
400 1:39 4:30 7:54 15:04
500 1:20 3:39 6:26 12:17
600 1:07 3:04 5:24 10:20
700 0:57 2:38 4:39 8:54
800 0:50 2:18 4:04 7:48
900 0:44 2:02 3:37 6:56
1000 0:39 1:50 3:15 6:14
1200 0:32 1:30 2:41 5:11
1400 0:26 1:16 2:17 4:25
1600 0:22 1:06 1:59 3:50
1800 0:19 0:58 1:45 3:23
2000 0:17 0:52 1:33 3:01
2500 0:12 0:40 1:13 2:22
3000 0:09 0:32 1:00 1:57
3400 0:08 0:25 0:50 1:40
4000 0:06 0:23 0:43 1:25
4500 0:05 0:20 0:38 1:15
Recharge
Hours
3 9 15
27