background image

3

VFC 15-150 / VFC 45-225

NATURAL GAS coNveRSioN PARTS KiT# P-176

120-170 R2

1. 

Turn off the boiler’s gas shut off valve. with a small (1/8” or 3 mm) flat 

screwdriver, open the inlet gas supply pressure test port by turning its center-

screw 1 full turn counterclockwise. attach a manometer to the pressure 

test port and turn on gas to appliance. static manometer reading should be 

ideally 7” w.c. for natural Gas. Minimum and maximum static pressure should 

be between 3” and 14” w.c. Monitor pressure throughout the comissioning 

procedure. Pressure may droop up to 1” to 2” w.c. at high fire. outlet Pressure 

(Manifold Pressure) should be between -0.04” w.c. and 0.00” w.c. with a 

target of -0.02” w.c.  

NOTE: 

The outlet pressure should only be measured 

with an accurate digital manometer. Consult factory before considering field 

adjustment.

2. 

Turn the high Fire (Gas:air ratio) screw one turn anti-clockwise (riching 

direction) using a small flat screwdriver.

3. 

set a load as Manual Control and run the boiler at the maximum firing rate 

(150 or 225 MBh as applicable). This load should be large enough to allow the 

boiler to operate at high fire for 20 plus minutes. Take note of what the load 

was set for before you change it to Manual Control.

4. 

do not insert your analyzer yet – wait until after step# 6.

5.   

at full-fire, the flame should be a blue-orange mix. If the flame is bright orange 

further adjust (clockwise) the high Fire (Gas:air) ratio screw until you obtain a 

blue-orange flame.

6. 

with a combustion analyzer probe in the flue gas test port, turn the high Fire 

(Gas : air ratio adjustment) screw clockwise 

(see diagrams on this page)

 

to achieve results. This screw offers very fine adjustment, and may require 

several turns. 

NOTE:

 Clock the gas meter to confirm full maximum rating plate 

input. Check the measured results with Table 3 - high Fire.

 

There is often backlash when you adjust the (Gas:air) ratio screw, so small 

adjustments (e.g. 1/4 turn or less per movement,) should be made, with 

sufficient time between adjustments for the analyzer to read the adjustments.

7. 

In the Manual Control mode adjust the firing rate to low Fire (15 / 45 MBh 

as appropriate). adjust the low Fire (Zero-offset) adjustment screw until your 

analyzer readings are within the range shown in Table 2.

  

NOTE: 

This adjustment is very sensitive, only small movements, e.g. 1/4 turn 

per adjustment, reducing to much smaller steps as the target is approached as 

applicable. wait 2-3 mins before making another adjustment.

  

NOTE:

 The effect of the low Fire screw is reversed: Clockwise richens the 

mixture and counter clockwise leans the mixture.

8. 

reset the boiler to high Fire and recheck the analyzer readings with Table 2.

9. 

reset the boiler to low Fire and recheck the analyzer readings with Table 2.

10. 

Turn Manual Control off by setting the load to its previous setting and remover 

the jumper. all the programmed settings will be restored and the load will 

operate as it did previously.  Turn off the gas supply, remove the manometer 

and close the gas pressure test port.

11. 

restore gas supply by opening the gas control valve, and using an approved 

leak detection solution, soap test all joints.

clocking the Meter 

(Natural Gas)

1.

  Turn off all other appliances and 

pilots

2.

  Turn on the boiler and set the 

boiler to high fire. ensure the 

boiler has a large load to heat so 

that the boiler will not shut off.

3. 

with a stop-watch, record 

the number of seconds for the 

smallest dial to make 1 full 

revolution.

4.

  CFh = (3600 x dial size) / 

seconds

5.

  CFh x 1000 (check local Btu 

content) = Input Btu’s

NOTE: 

  For 2 PsI meters multiply CFh x 

1.097

  For Metric meters multiply CFh x 

35.3

  For 2 PsI metric meters multiply 

CFh x 1.097 x 35.3

  For altitude above 4,500’ deduct 

2% per 1,000' of altitude from the 

Input Btu’s

Zero-offset adjustment screw

Gas:Air ratio adjustment screw

Reviews: