background image

OPERATING INSTRUCTIONS

22

V-10 TOUCH SCREEN BOILER CONTROLLER

The BoilerNet Interface utilizes a 2-wire CAN-bus communications interface 

between the boilers. BoilerNet wiring must be installed in compliance with the 

published standards, ISO 11898 or SAE J2284. A suitable cable, compliant with 

the same standards must be used.
The general specifications for this cable are:

• 

24 AWG shielded twisted pair

• 

9 twists / ft

• 

Capacitance 12.5pF/ft (cond./cond.)

• 

Resistance 25.5 ohms/1000 ft

Network wiring tips:

• 

The “Boiler Net +” and “Boiler Net –“ are polarity sensitive and must not be 

crossed.

• 

The Boiler Network wiring must only be installed in a “Daisy Chain” format 

where the network wiring goes from the first boiler to the second to the third to 

the fourth and so on.

• 

When using shielded pair wire ensure the shielding is only grounded at one 

end of the “Daisy Chain”. If the shielding is grounded in multiple locations (i.e. 

at each boiler or at the first and last boiler,) the shielding becomes ineffective 

and in some cases increases the electromagnetic interference affecting the 

communication signal.

The termination jumper (JA02) needs to be removed from the boiler controller 

boards that are NOT the first or last boiler of the BoilerNet chain. For example, in 

a two boiler network JA02 must be left installed in both controllers and in a three 

boiler network the JA02 must be removed on the middle boiler only.
Please contact IBC if any additional information is required.

1.7.11 Internet Networking

Internet Protocol (IP) networking based features are supported via the standard 

RJ 45 Ethernet jack on the back of the controller board. Web Browser access for 

set up, monitoring and control of the boiler and BACnet capabilities are examples 

of features enabled by connecting the controller to an IP network via the Ethernet 

jack.
The IP network settings are available via the 

Network Settings

 selection on the 

System Settings

 screen (see section 1.5.5.2). On the Network Settings screen 

the 

TCP/IP

 group of parameters includes the basic settings required to connect 

to an IP network. By default 

DHCP

 is selected. When 

DHCP

 is activated the 

other four entries are not required and their entry boxes are disabled. When 

the particular installation requires that the boiler be assigned a fixed IP address 

then Manual must be selected and the boiler’s 

IP Address

, the 

Net Mask, DNS 

Server 

address and 

Gateway 

address must be entered manually.

The controller supports standard 100 Base T data rates over typical CAT5 

or CAT6 wiring. Connection to wireless networks can be supported using an 

inexpensive wireless access point device connected to the Ethernet jack. The 

wireless access point device must be configurable to operate in client mode.

Contact IBC for currently available access point device suggestions.

WARNING

Disconnect electrical power 

to the boiler before removing 

the circuit board cover.

Summary of Contents for V-10

Page 1: ...OPERATING INSTRUCTIONS www ibcboiler com V 10 TOUCH SCREEN BOILER CONTROLLER This Manual is also available in French contact IBC or visit our web site www ibcboiler com...

Page 2: ......

Page 3: ...5 5 2 SYSTEM SETTINGS 10 1 5 6 DIAGNOSTICS 10 1 6 SEQUENCE OF OPERATION 12 1 6 1 STANDBY 13 1 6 2 PURGING 13 1 6 3 IGNITION 13 1 6 4 HEATING 14 1 6 5 CIRCULATING 14 1 6 6 ERROR MODE 15 1 7 OTHER OPERA...

Page 4: ......

Page 5: ...card or USB stick Superior warning messages while setting up the control Advanced Error messages with visual display on the Home Screen Internet LAN connectivity BACnet with activation CONTROL When th...

Page 6: ...rea consisting of the screen title bar at the top and a boarder surrounding the active area At the bottom of the display there is space reserved for the boiler status bar Prior to any interaction with...

Page 7: ...ry buttons are used to set the load type Radio buttons are used to select a setting from a list of options and can be used in conjunction with entry boxes A check box is used to select whether a speci...

Page 8: ...viewable will scroll with the side bar You can also tap the arrows at either end of the Slide Bar to move the bar up or down 1 3 2 6 COMMON BUTTON ICONS Save will save the displayed settings and retu...

Page 9: ...settings The User Setup selection provides a relatively simple interface allowing for the adjustment of settings relevant to the user while Installer Setup gives field access to the full functionalit...

Page 10: ...2 Express Setup Express Setup is a quick and simple method to set all the necessary parameters for most single boiler installations Express Setup sets parameters to default values including all the a...

Page 11: ...s of a load or to add settings for a programmed load Outdoor design temperature can be adjusted in the Installer Menu 1 5 3 Load Status Touching one of the Load 1 to 4 buttons will bring up a status d...

Page 12: ...previously known as Load Pairing feature Refer to section 1 7 2 System Settings leads to a menu screen where the Site Settings Network Settings Security Licensing and Backup Restore selections are av...

Page 13: ...pump to operate for a period of time to transfer heat that is stored in the boiler s heat exchanger into the hot water tank This feature is adjustable in seconds from 0 to 900 15 min If the load has...

Page 14: ...e time manual pump purge and the variable speed output control settings The Network Settings screen is used to assign the boiler its ID address and network configuration to support multi boiler operat...

Page 15: ...sors status screen displays the current active value for each of the pressure sensors the water Flow Rate VS Load Duty Cycle and the Altitude If a sensor is not connected to the controller it will dis...

Page 16: ...history is not cleared Reset Factory Defaults will take approximately 2 minutes to complete Over time the touch pad calibration can drift slightly resulting in the touch locations being out of line wi...

Page 17: ...iler target water temperature 1 2 the Supply Differential The cut off temperature levels are specific for each load for space heating they are determined using the preset target plus 1 2 of the Supply...

Page 18: ...ater temperature is 1 2 of the supply differential below setpoint temperature The boiler can also enter the Circulating mode during transition from any high temperature load e g DHW at 180 F to the co...

Page 19: ...the boiler s operation when more than one load has been defined Typically loads declared as DHW receive significant but not absolute priority Multiple heating loads with varying temperature targets ar...

Page 20: ...id equal ratings NOTE the priority scale values do not need to add up to 100 they are relative only to each other 1 7 2 Load Combining The controller allows two loads of compatible temperature setting...

Page 21: ...ottle has no effect once the loads have been combined 1 7 2 1 CONSIDERATIONS FOR COMBINING LOADS The Primary and Secondary loads must have compatible temperature parameter settings or the Secondary lo...

Page 22: ...exes the boiler supply temperature according to characterized heating curves that are automatically called up through the load declaration process Curves are provided for each of the radiation termina...

Page 23: ...baseboards sink very little heat when operated below 90 F 32 C application of a full reset curve e g 160 F 71 C right down to a 70 F 21 C room target would cause boiler cycling in light to moderate h...

Page 24: ...upied mode the DHW load is turned off while a Reset Heating load will have it s circulating water temperature lowered by reducing the Indoor Setpoint to 50 F 10 C Set Point controlled loads are not ad...

Page 25: ...oads with the same priority logic and sequencing 1 7 9 Alarm Contacts The controller provides a relay dry contact connection to indicate the boiler s alarm state externally This can be used for exampl...

Page 26: ...work the JA02 must be removed on the middle boiler only Please contact IBC if any additional information is required 1 7 11 Internet Networking Internet Protocol IP networking based features are suppo...

Page 27: ...outer connecting the boiler s local area network to the Internet have its port forwarding settings configured to forward port 80 to the boiler s local IP address In this case the remote browser will a...

Page 28: ...OPERATING INSTRUCTIONS 24 V 10 TOUCH SCREEN BOILER CONTROLLER DIAGRAMS ELECTRICAL WIRING DIAGRAM 2 0 2 1...

Page 29: ...rm 2 TB2 7 Therm 3 TB2 8 or Therm 4 TB2 9 depending on the load it is intended to control Power stealing thermostats take a small amount of current from the 24 VAC to operate their internal electronic...

Page 30: ...e white black black Vent High Limit Switch Upper Vessel High Limit Switch Water High Limit Switch white yellow black yellow red white red white white white white white black yellow yellow black black...

Page 31: ...PERATING INSTRUCTIONS V 10 TOUCH SCREEN BOILER CONTROLLER CONTROLLER BOARD LAYOUT 2 3 NOTE See Instruction Sheet for instructions on installing a V 10 Touch Screen Boiler Controller Re Order Part 500...

Page 32: ...OPERATING INSTRUCTIONS 28 V 10 TOUCH SCREEN BOILER CONTROLLER SEQUENCE OF OPERATION 2 4...

Page 33: ...NOTES...

Page 34: ...NOTES...

Page 35: ...REVISION HISTORY R1 JULY 2014 Initial release R2 JULY 2015 Address update...

Page 36: ...IBC Technologies Inc 8015 North Fraser Way Burnaby BC Canada V5J 5M8 Tel 604 877 0277 Fax 604 877 0295 www ibcboiler com 120 198 R2 July 2015 IBC Technologies Inc 2015...

Reviews: