INSTALLATION AND OPERATION INSTRUCTIONS
5-6
SL 20-115 G2 MODULATING GAS BOILER
SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS
5.3 TROUBLESHOOTING
SYMPTOM
DIAGNOSIS
REMEDY
MAXIMUM IGNITION
TRIALS ERROR
Touch Screen Message:
Error – Ignition Failure after 3
tries
Boiler has failed to ignite on 3
successive attempts. Boiler in
lockout for 1 hour, then repeats
3-try seq. Consult service
technician if error recurs.
No spark when igniting.
Igniter probe/flame
sensor disconnected.
Check that igniter lead is secure at the control module
and at the probe.
Manual gas shutoff is
closed or gas line not
fully purged.
Check for gas flow. Open manual gas shutoff and
reset boiler.
Gap between igniter
probe rods is too large
or too small.
Adjust ignitor probe rod gap between 1/8th and
3/16th (3.2-4.7mm).
Spark, but no ignition.
Check spark module is sending power to gas valve
– close gas supply, then disconnect (black) electric
housing from face of gas valve, gently spread plastic
tabs to open, and look for 24vac voltage during an
ignition cycle. Replace module if no current detected
Boiler ignites, but shuts
off at the end of the
ignition trial. Improperly
grounded pressure vessel/
burner or unserviceable
ignition lead or spark
module.
• Ensure pressure vessel is grounded.
•
Check the igniter probe/flame sensor is electrically
isolated from the vessel, and its ceramic insulator
is intact.
• Replace ignition lead
• Replace spark module
HI LIMIT CUTOFF
TEMPERATURE ERROR
Touchscreen message:
Error – Water High-Limit
Exceeded
Water temperature
exceeds hi-limit. Boiler is
in hard lockout mode.
See Section 5.2.4.
LOW WATER CUTOFF
ERROR
Touchscreen message:
Error - Low Water Cutoff
The Safety and Ignition
module has detected a
low water condition.
See Section 5.2.4.
5.3.1 Using Control Module Errors Displayed
WARNING
Never attempt to repair the
control module (circuit board). If
the control module is defective,
replace it immediately.
Summary of Contents for SL 14-115 G3
Page 71: ...6 3 DIAGRAMS SL 14 115 G3 SL 20 160 G3 SL 30 199 G3 MODULATING GAS BOILERS...
Page 73: ...6 5 DIAGRAMS SL 14 115 G3 SL 20 160 G3 SL 30 199 G3 MODULATING GAS BOILERS...
Page 75: ...6 7 DIAGRAMS SL 14 115 G3 SL 20 160 G3 SL 30 199 G3 MODULATING GAS BOILERS...
Page 81: ...SERVICE RECORD DATE LICENSED CONTRACTOR DESCRIPTION OF WORK DONE...
Page 82: ...NOTES...
Page 83: ...NOTES...