1-29
INSTALLATION
SFC BOILER / WATER HEATERS - SFC 199
1.7 DOMESTIC HOT WATER SYSTEM
WARNING
CAUTION
WATER HEATER INSTALLATION GUIDELINES
ADJUSTABLE TEMPERATURE SETTING
°
Hotter water increases the risk of scald injury. Before changing the temperature setting, see
instruction manual.
°
This unit must be installed in accordance with local codes, if any; if not follow the National
Fuel Gas Code, ANSI Z223.1/NFPA 54, or the Natural Gas and Propane Installation Code,
CAN/CSA B149.1, as applicable.
°
Failure to correctly install and operate this appliance can result in severe personal injury
or death.
°
The unit shall have a pressure relief valve installed within 6” [152mm] of the DHW HOT
outlet connection.
Refer to the unit’s User Manual before operating the relief valve.
°
The unit requires a pressure relief valve identified with the ASME V or HV symbol and
set to relieve at or below 150psi of domestic water pressure and a minimum relieving capacity
of 199,000 Btu/hr with 3/4” NPT threads. For safe operation of the unit, the relief valve
must not be removed from its designated point of installation or plugged.
°
Read and follow warnings and instructions.
°
Touch the panel above the dot twice, then touch the Faucet . . Adjust the water temperature
with the Plus + and Minus – then touch the Return button to save the changes.
BURN
HOT
DANGER
°
Water temperature over 125°F (52°C) can cause severe burns instantly
or death from scalds.
°
Children, disabled, and elderly are at highest risk of being scalded.
°
See instruction manual before setting temperature at water heater.
°
Feel water before bathing or showering.
°
Temperature limiting valves are available, see manual.