INSTALLATION AND OPERATION INSTRUCTIONS
1-12
SFC BOILER / WATER HEATERS - SFC 199
You must follow the installation instructions, clearances and wall thickness
requirements recommended of the approved vent termination manufacturer.
Approved Side Wall Termination Kits are listed below: (Alternative vent
termination kits must be submitted to IBC for approval prior to installation.)
•
Ipex - #196984 – 2" PVC low profile termination kit
•
Ipex - #196985 – 3" PVC low profile termination kit
Figure 10: Non-Concentric kits - Ipex #196984 2” PVC and #196985 3” PVC
Figure 11a: Horizontal Concentric Termination - Two Kits
Figure 11b: Horizontal Concentric Termination - Single Kit
WARNING
The vent for this appliance
must not terminate:
1. Over public walkways.
2. Near soffit vents or crawl
space vents or other areas
where condensate or vapor
could create a nuisance or
hazard or cause property
damage.
3. Wherever condensate
vapor could cause damage
or could be detrimental to the
operation of regulators, relief
valves, or to other equipment.