![background image](http://html1.mh-extra.com/html/ibc-water/as1029mp-cl/as1029mp-cl_installation-and-operating-instructions-manual_3227771017.webp)
AS1029MP-CL
Page
17
The ideal location for the unit is above and not more
than 6.1m (20ft) from the drain. For such installations,
using the appropriate adaptor fitting (supplied),
connect 12mm (1/2”) plastic tubing to the drain line
connection located on the top of the valve.
If the unit is located more than 6.1m (20ft) from the
drain, use 20mm tubing for runs up to 12.0m. You
may elevate the line up to 1.8m providing the run
does not exceed 4.5m and the water pressure at the
conditioner is not less than 280kPa (40psi.) You may
elevate an additional 500mm for each additional
70kPa. (10psi) of water pressure.
When the drain line is elevated and empties into a
drain which is below the level of the control valve,
form a 170mm (7 inch ) loop at the drain end of the
line so that the bottom of the loop is level with the
drain line connection. This provides an adequate
siphon trap.
If the drain empties into an overhead sewer line, a
sink-type trap must be used.
Caution
Never connect the drain line into a drain,
sewer line or trap. Always allow an air gap
between the drain line and the wastewater
to prevent the possibility of sewage being
back-siphoned into the conditioner.
Important Installation Details
The control valve, fittings and/or bypass are designed
to accommodate minor plumbing misalignments but
are not designed to support the weight of the system
or the plumbing.
Do no use Vaseline, oils, other hydrocarbon lubricants
or spray silicone anywhere. A silicone lubricant may
be used on black o-rings but is not necessary.
Avoid
any type of lubricants, including silicone, on the
clear lip seals.
The nuts and caps are designed to be unscrewed or
tightened by hand or with the special plastic wrench.
Do not use a pipe wrench to tighten or loosen nuts or
caps. Do not place a screwdriver in the slots on caps
and/or tap with a hammer.
Do not use pipe dope or other sealant on threads.
Use teflon tape on threaded inlet, outlet and drain
fittings.Teflon tape is not necessary on the nut
connection or caps because of o-ring seals.
After completing any valve maintenance involving
the drive assembly of the drive camp assembly
and pistons, press and hold NEXT and REGEN
buttons for 3 seconds or unplug power source
jack from the printed circuit board (black wire)
and plug back in
. This resets the electronics and
establishes the service piston position. The display
should flash all wording, then flash the software
version and then reset the valve to the service
position.
All plumbing should be done in accordance with local
plumbing codes. The pipe size for the drain line
should be a minimum of 12mm.
Solder joints near the drain must be done prior to
connecting the drain line flow control fitting. Leave at
least 150mm (6”) between the drain line control fitting
and solder joints when soldering pipes that are
connected on the drain line control fitting. Failure to
do this could cause interior damage to the drain line
flow control fitting.
When assembling the installation fitting package (inlet
and outlet), connect the fitting to the plumbing system
first and then attach the nut, split ring and o-ring.
Heat from soldering or solvent cements may damage
the nut, split ring and o-ring. Solder joints should be
cool and solvent cements should be set before
installing the nut, split ring or o-ring. Avoid getting
primer and solvent cement on any part of the o-rings,
bypass valve or control valve.
Position the softener within 1 ½ metres of a 10 amp
GPO. The transformer is connected into the plug
socket on the back of the valve control panel. Do not
Figure 5 - Air Gap Installation
Not In Bypass In Bypass
Summary of Contents for AS1029MP-CL
Page 3: ...AS1029MP CL Page 3...
Page 5: ...AS1029MP CL Page 5...
Page 11: ...AS1029MP CL Page 11 MODEL AS1029MP WATER SOFTENER WITH CONTROL VALVE SERIES MODEL WS1EI...
Page 19: ...AS1029MP CL Page 19...
Page 20: ...AS1029MP CL Page 20 WS1EI Screen Display Information And Programming Instructions...
Page 22: ...AS1029MP CL Page 22 General Regeneration Error Screens Status...
Page 29: ...AS1029MP CL Page 29 SPARE PARTS AND SERVICING INSTRUCTIONS...
Page 39: ...AS1029MP CL Page 39 flow diagram backwash Flow Diagram Downflow...
Page 40: ...AS1029MP CL Page 40 flow diagram downflow brine Flow Diagrams Rinse and Fill...
Page 41: ...AS1029MP CL Page 41 flow diagram rinse flow diagram fill WS1 Wrench Order No V3193 01...
Page 49: ...AS1029MP CL Page 49 INJECTOR PERFORMANCE CURVES...
Page 50: ...AS1029MP CL Page 50...
Page 52: ...AS1029MP CL Page 52...