Our AF Series Filters are fully automatic incorporating Backwash, Rinse-Pause, Fast Rinse
and Service Cycles, controlled by cam switches in the timer. Frequency of Backwashing can
be altered from that suggested in the Commissioning Section, if actual site conditions
dictate alterations.

 

 

Water enters the unit through the multi-port valve and passes through the media,
underdrain gravel and the distributor leaving through the multi-port valve.

 

 

Multi-Media Filters

 

Remove filterable turbidity at high flow rates several times the flow rate of conventional
filters, producing clear filtered water down to 10 micron through the stratified bed without
chemical flocculation. No additional pumping is necessary for Backwashing, as the
Backwash water required is normally only 80-90% of the service flow rate. Multi Media Filter
capacity is many times that of conventional filtration due to utilisation of the entire stratified
bed, resulting in low operating costs.

 

 

This unit is not designed to remove colloidal matter, a plant capable of coagulation is
required in such cases.

 

 

Operating Parameters

 

Water Temperature

5ºC - 48ºC

 

Water pH

5.5 - 9.0

 

Water Pressure

205 - 690 kPa

 

Oil

Free of Hydrocarbons

 

 

AF SERIES FILTERS

 

 

Table 2

 

 

OPERATING PRINCIPLE

TYPE

MODEL

CONTINUOS

FLOW RATE

L.P.M

PEAK FLOW

RATE L.P.M

BACKWASH
FLOW RATE

L.P.M

VALVE

APPROX.

WEIGHT

KG

OPERATING

PROCEDURES

Multi-
Media

AFM

20-180

120

160

114

180

320

Water Temp: 5ºC - 48ºC
Water pH: 5.5 - 9.0
Suspended Solids:
        Max 100 mg/l
        (Refer factory)
Iron: No Effect
Oil:  Free of
        Hydrocarbons

NOTE: Not recommended
for Colloidal Sediment
removal

Valve

180

Inlet
(mm)

40

Outlet
(mm)

40

Drain
(mm)

40

Operating Pressure:  205 - 690 kPa
Temperature:  5

º

C - 48

º

C                             Electrical:  240V 50Hz 3 watts maximum

Warning:  A pressure reduction valve should be installed if water pressure is greater than 600kPa.
Warning:  A pressure reduction valve should be installed if water hammer prevails.

Table at left shows recommended MINIMUM plumbing sizes.
FAILURE TO OBSERVE WARNING WILL VOID WARRANTY

Summary of Contents for AFM20-180

Page 1: ...TRUCTIONS Model AFM20 180 Serial No Telephone 07 3219 2233 Facsimile 07 3219 2266 Email sales ibcwater com au Website www ibcwater com au FILTRATION WATER TREATMENT PRODUCTS for commercial industrial...

Page 2: ...tion of the entire stratified bed resulting in low operating costs This unit is not designed to remove colloidal matter a plant capable of coagulation is required in such cases Operating Parameters Wa...

Page 3: ...following instructions are provided as a general guide The filter requires a 10amp 240 volt GPO The filter installation must be protected from the elements FIG 4 INSTALLATION SINGLE TANK SOFTENER INST...

Page 4: ...M Sand and D3 Slowly fill the tank Step 4 To obtain optimum performance from your unit exercise particular care in ensuring that each grade of media is levelled evenly over the previous layer Step 5 F...

Page 5: ...Page 5...

Page 6: ...again and rotate anti clockwise to the fast rinse position and release Verify that the spindle has moved to its correct position as indicated in the following illustrations Step 4 Allow the red knob...

Page 7: ...with the duty conditions for maximum economy NOTE This is only a guide for initial setting and should be altered to suit each individual installation in accordance with load conditions of the raw wat...

Page 8: ...the same number of hours Time indicated as BLACK ARROW will no longer be correct Each additional pin either pulled out or pushed in equals 3 minutes SET BACKWASH TIMING Pull pins as shown for desired...

Page 9: ...min 2 pins outward Valve Position MANUAL OPERATION Push in RED KNOB and turn COUNTERCLOCKWISE to the START position Release Unit will then go through a complete regeneration as programmed VALVE AND CY...

Page 10: ...Page 10 ELECTRICAL DIAGRAMS Wiring Diagram 450 Impulse Timer Wiring Diagram 440 Six Day or Seven Day Timer...

Page 11: ...Page 11 FLOW SCHEMATIC...

Page 12: ...Page 12 REPLACEMENT PARTS...

Page 13: ...0 gpm BSPT 36 1076297 PWA assembly 962 1034712 15 gpm NPT 37 ZHDW4152 Marker strip 11 20 1034713 15 gpm BSPT 38 650022 10 Terminal block 1034714 25 gpm NPT 39 SCS 0064 Screw 4 40 x 5 8 round head 1034...

Page 14: ...60Hz 100V 50Hz 230V 50Hz Optional standard electrical rating 962 Controller 230V 50 60Hz Electrical cord when furnished with standard rating 6ft 3 wire with plug Electrical Connection Terminal strip S...

Page 15: ...ory and rotation checked at this time However resetting may be necessary from time to time should the unit fail to draw brine Setting is simple index position to service position fully in switch off p...

Page 16: ...e 16 MEDIA PLACEMENT MULTI MEDIA SEDIMENT FILTER Sequence in Tank AFM20 1st in bottom of tank 30kg 6 gravel 1 Bag 2nd 44kg D1 2 Bags 3rd 44kg D2 2 Bags 4th 80kg 7M Sand 4 Bags 5th 50kg D3 2 Bags Table...

Page 17: ...AGE UNIT WILL NOT BACKWASH AUTOMATICALLY Page Eighteen UNFILTERED WATER TO SERVICE Page Eighteen LEAK TO DRAIN Page Nineteen INSUFFICIENT SERVICE FLOW RATE Page Nineteen TROUBLE SHOOTING GUIDE AFM20 1...

Page 18: ...down and fully engaged F VALVE MOTOR MICRO SWITCH NOT OPENING OR CLOSING adjust micro switch stack Fig 20 G VALVE MOTOR MICRO SWITCH BURNED OUT replace micro switch H VALVE MOTOR MICRO SWITCH NOT OPE...

Page 19: ...located at drain and of plunger A UNIT MAY BE FOULED WITH SUSPENDED SOLIDS backwash and check again B SERVICE INLET OR OUTLET VALVE NOT FULLY OPENED ensure they are opened C PISTON OUT OF POSITION re...