![background image](http://html1.mh-extra.com/html/ibc-water/afm20-180/afm20-180_installation-and-operating-instruction_3223125014.webp)
Page 14
SPECIFICATIONS
Hydrostatic test pressure ……………………………………………………………………………………………. 250 psi (17.2
bar)
Working pressure ……………………………………………………………………………………….. 20 - 100 psi (1.38 - 6.89
bar)
Standard electrical rating …………………………………………………………………………………………………….
120V/60Hz
Optional standard electrical rating (Timers) ………… 24V/50Hz, 24V/60Hz, 120V/50Hz, 100V/60Hz, 100V/50Hz,
230V/50Hz Optional standard electrical rating (962 Controller) …………………………………………………………………...
230V 50/60Hz
Electrical cord (when furnished, with standard rating ………………………………………………………….. 6ft, 3 wire with
plug
Electrical Connection …………………………………………………………………………………………………….. Terminal
strip
Standard plumbing connection ………………………………………………… 1 - 1/2 in NPT inlet, outlet top and bottom of
tank
1/2 in NPT brine; 3/4 in
NPTdrain
Rubber parts ………………………………………………………………………………………... Compound for cold water
service
Valve body …………………………………………………………………………………………………………………………..
Brass
Injector ………………………………………………………………………………….. 3 sizes available: A, B, C (Refer to page
20)