ibaPADU-S-IT-16
Manual
Issue 1.10
57
11.2
ibaPDA-V6
With ibaPDA-V6, you can configure, capture and record the analog and digital signals of
the connected modules.
Important note
You need an FO card with input links and output links of the FOB-D type with Firmware be-
ginning with version V2.00 (build 172). Otherwise, you need to do a Firmware update. You
find a description (in the ibaFOB-D manual) and the latest Firmware on the CD that is in-
cluded in delivery.
Important note
If in ibaPADU-S-IT-16, the ibaLogic runtime system for pre-processing the signals is ena-
bled, you need to pay attention that all settings and ibaPDA and ibaLogic fit each other. The
following parameters have to be considered:
-
ibaLogic-V4:
Sampling time of the buffered input signals,
ibaPDA-V6:
Time base for the PADU-S module
-
ibaLogic-V4: Configuration of the debounce filter (filter type, debounce filter)
ibaPDA-V6:
Configuration of the debounce filter
-
ibaLogic-V4:
FO protocol (external)
ibaPDA-V6:
FO protocol (32Mbit Flex)
ibaPADU-S-IT-16: Switch position S1
≥ 1
11.2.1
Configuration in the I/O Manager
Start ibaPDA, open the I/O Manager and proceed as follows:
1.
Look in the I/O Manager for the link of the FOB-D card, ibaPADU-S-IT-16 is connected
to. Click with the right mouse button on the link. The submenu is opened.
Choose “Au-
todetect“.
If ibaPDA detects the device automatically, the device and the connected modules are
listed in the module tree.