Under
“Module Settings“, ibaPADU-S-IT-16 is always activated.
If “Buffered Access“ is enabled, the imported values are buffered and supplied to the pro-
gram as Arrays. The smallest possible Interval of ibaLogic is 1 ms. If you want to measure
signal values with sampling rates smaller than 1 ms, you need to record the signal values
“buffered“.
Note
You need to apply the “Buffered Access“ by clicking on the <Apply> button. Only then, you
will see additional signals in the signal tree that can be configured as output or input re-
sources.
In the “Signal Settings“ field, you can choose the input signals for the chosen module on
the
“Input“ tab and the output signals on the “Output“ tab by ticking the boxes.
The chosen signals have to be applied by clicking on the <Apply> button. The signals then
appear in the signal tree on the left and can be assigned. Additionally, you can access fur-
ther signals in the signal tree, e.g. Sample Time.
The meaning of the signals:
Signal
Meaning
Inputs
DI_24V_Ch[0
0…07]
Digital input signals of ibaPADU-S-IT-16
StatusIn
Status information about the plugged input mo-
dule (for output module without function):
0 = Module not initialized
1 = Module running
>1 = Mistake (e.g. module cannot be initialized)
StatusOut
Status information about the plugged module (for
input module without function):
0 = Module not initialized
1 = Module running
>1 = Mistake (e.g. module cannot be initialized)
Invalid_In_ X[2..5]
Invalid_out_X[2..5]
Invalid_In_FO
Invalid_Out_FO
Invalid_In_App
Invalid_Out_App
Err_Sample_Clk
Err_App_Crash
Status signals for service purposes
Outputs
DebType_Ch[
00…07]
Debounce filter for digital signals
DebTime_Ch[00...07]
Debounce time for the single digital signal
SampleTime
Sample time for buffered access
Additional signals for buffered access
SampleTime_Sec
Time period since system start in seconds
SampleTime_Frac
Fractions of this second
(1 s = 4,294,967,295 fractions)