2nd Stage (Y2):
If space temperature continues to rise,
thermostat Y2 demand will be initiated. Contact Y2 will
close, sending a 24--v signal to CTB’s TSTAT terminal
strip at Y2. An internal path passes this signal to
connector DDC/TSTAT pin 6. A harness wire carries this
signal to Fan Speed Relay board pin J1--3. Relay K2 is
energized. The relay board’s output to VFD at pin J2--2 is
de--energized and the output at J2--3 is energized, causing
the VFD to shift its output to the indoor fan motor to
60HZ. The indoor fan motor ramps up to full/high speed
operation.
When the space temperature drops to satisfy thermostat
Y2 demand, contact Y2 opens de--energizing terminal Y2.
Relay K2 is de--energized, removing the VFD input at
terminal 15. Fan Speed Board output at pin J2--2 is
restored to the VFD at terminal 14; VFD shifts back to
40HZ output to the indoor fan motor and motor shifts
back to reduced speed operation.
Heating
When the thermostat initiates a call for 1st Stage Heating
by closing its W1 contacts, a 24--v signal is conveyed to
the CTB’s TSTAT terminal strip at W1. An internal path
passes this signal to connector DDC/TSTAT pin 5. A
harness wire carries this signal to Fan Speed Relay board
pin J1--2. Relay K1 is energized. The relay board’s output
to VFD at pin J2--3 is energized, providing a 24--VDC
signal to VFD terminal 15. The VFD starts the indoor fan
motor, runs at 60HZ for full/high speed operation.
When space temperature rises to satisfy the thermostat
W1 demand, contact W1 opens de--energizing terminal
W1. Relay K1 is de--energized. The relay board output at
J2--3 to the VFD is removed.
40RU, 50--Series:
Indoor fan motor ramps down to stop.
48--Series:
The IGC’s fan--off delay sequence will energize
relay K3 for 45--seconds, causing the VFD to operate the
indoor fan motor at 40HZ (low speed) for 45--seconds, then
indoor fan motor will ramp down to stop.
N/A
1
J2
24vdc
6
J2
2
3
Lo Spd
Hi Spd
K1
K2
K2
K3
K4
JMP2
K3
K1
K1
K2
K3
K4
W1
C
Y2
HUMID
G
2
1
J1
3
4
5
4 & 5
JMP1
COM
VFD TERMINAL
YEL
WHT
11
10
12 13 14 15 16
C13807
Fig. 11 -- Connection Schematic – Fan Speed Relay Board and VFD.
Summary of Contents for ultraDRY
Page 1: ...O M manual PD 02 22 2020 v 5 71 ultraDRY outside air solutions ...
Page 51: ...iAIRE OM manual iAIRE LLC 51 ...
Page 70: ...iAIRE LLC iAIRE OM manual 70 ...
Page 71: ...iAIRE OM manual iAIRE LLC 71 ...
Page 78: ...iAIRE LLC iAIRE OM manual 78 APPENDIX A CAPACITY CONTROL DEVICE ...
Page 79: ...iAIRE OM manual iAIRE LLC 79 ...
Page 80: ...iAIRE LLC iAIRE OM manual 80 ...
Page 81: ...iAIRE OM manual iAIRE LLC 81 CALL US TODAY 800 231 3112 TO DISCUSS YOUR APPLICATION ...
Page 84: ...iAIRE LLC iAIRE OM manual 84 APPENDIX B VFD ...
Page 85: ...iAIRE OM manual iAIRE LLC 85 Operating Instructions SMVector Frequency Inverter ...
Page 129: ...iAIRE OM manual iAIRE LLC 129 APPENDIX C ICM LOW AMBIENT CONTROL ...
Page 131: ...iAIRE OM manual iAIRE LLC 131 APPENDIX D SPACE SENSOR ...
Page 138: ...iAIRE LLC iAIRE OM manual 138 APPENDIX E SPLIT SYSTEM PIPING REQUIREMENTS ...
Page 139: ...iAIRE OM manual iAIRE LLC 139 iAIRE SPLIT SYSTEM PIPING CHART ...
Page 153: ...iAIRE OM manual iAIRE LLC 153 Page 2 of 4 ...
Page 154: ...iAIRE LLC iAIRE OM manual 154 Page 3 of 4 ...
Page 155: ...iAIRE OM manual iAIRE LLC 155 Page 4 of 4 ...
Page 156: ...iAIRE LLC iAIRE OM manual 156 APPENDIX F SPLIT SYSTEM DAT SENSOR INSTALLATION ...
Page 158: ...iAIRE LLC iAIRE OM manual 158 APPENDIX G MODULATING GAS VALVE ...
Page 159: ...iAIRE OM manual iAIRE LLC 159 ...
Page 161: ...iAIRE OM manual iAIRE LLC 161 ...
Page 164: ...iAIRE LLC iAIRE OM manual 164 Mod Gas Heat Install I O M manual PD 03 25 2019 v 1 2 ...
Page 165: ...iAIRE OM manual iAIRE LLC 165 APPENDIX H SMOKE SENSOR ...
Page 172: ...iAIRE LLC iAIRE OM manual 172 APPENDIX J 24 7 TIMER ...
Page 173: ...iAIRE OM manual iAIRE LLC 173 ...
Page 174: ...iAIRE LLC iAIRE OM manual 174 ...
Page 175: ...iAIRE OM manual iAIRE LLC 175 ...
Page 176: ...iAIRE LLC iAIRE OM manual 176 ...
Page 177: ...iAIRE OM manual iAIRE LLC 177 ...
Page 178: ...iAIRE LLC iAIRE OM manual 178 ...
Page 179: ...iAIRE OM manual iAIRE LLC 179 ...
Page 180: ...iAIRE LLC iAIRE OM manual 180 ...
Page 181: ...iAIRE OM manual iAIRE LLC 181 ...
Page 182: ...iAIRE LLC iAIRE OM manual 182 ...
Page 183: ...iAIRE OM manual iAIRE LLC 183 APPENDIX K HIGH HEAT BOX ...
Page 188: ...iAIRE LLC iAIRE OM manual 188 ...
Page 191: ...iAIRE OM manual iAIRE LLC 191 ...
Page 197: ...iAIRE OM manual iAIRE LLC 197 ...
Page 198: ...iAIRE LLC iAIRE OM manual 198 15 APPENDIX B Heatco Application Guide ...
Page 200: ...iAIRE LLC iAIRE OM manual 200 ...
Page 201: ...iAIRE OM manual iAIRE LLC 201 ...
Page 202: ...iAIRE LLC iAIRE OM manual 202 ...
Page 203: ...iAIRE OM manual iAIRE LLC 203 ...
Page 208: ...iAIRE LLC iAIRE OM manual 208 ...
Page 209: ...iAIRE OM manual iAIRE LLC 209 ...
Page 215: ...iAIRE OM manual iAIRE LLC 215 APPENDIX L UPC BACNET INSTALLATION ...
Page 236: ...iAIRE LLC iAIRE OM manual 236 APPENDIX M BACNET TROUBLESHOOTING GUIDE ...