COBALT Pro

 Exposed Flush Valve  

Standard Operations

101819 / 101673

I-CON  Systems,  Inc.,  for  product  support  call  1-866-730-7192  or  visit  us  online  at  support.i-con.com                           

One or more products contained herein are protected by U.S. Patent with other undergoing the patent process www.i-con.com/patents

page 4

Rev 081723

ADJUSTABLE PARAMETERS

Range 

Adjusts the maximum range used to detect a user. The range can be adjusted from 6-54 inches. 

Exit Time 

Adjusts the amount of time an object must not be detected before the valve considers the user to have exited. 

 

The range can be adjusted from 0-15 seconds. 

Water Savings  

Adjusts the water volume savings in percent. 

Base Volume 

Adjusts the base volume. 

Adjusted by first pressing the Profile Selection button, and then adjusting using the water savings dial. 

Due to display limitations volumes are truncated on the display.

Fixture Type

Selectable Volume

Displayed Value

Urinal

0.125, 0.25, 0.5, 1.0 gallons

0.1, 0.2, 0.5, 1.0

Water Closet

1.1, 1.28, 1.6, 2.4, 3.5 gallons

1.1, 1.2, 1.6, 2.4, 3.5

Redetect Time 

Adjusts the amount of time a user must be out of range before another user can be detected. The range can be adjusted 

 

from 0-60 seconds.