J300
5
INSTRUCTION MANUAL
UV WAIT
POWER OFF
Tuning OK
Tuning NG
R-ERROR
COMM<*>
R-ERROR
INV . RUN
R-ERROR
INV . TRIP
R-ERROR
INV . TYPE
R-ERROR RD
LOCK
RESTART
ADJUST
. s
* * * *
. s
* * * *
Display
Other displays
Cause
Description
Communication error
*-1. Protocol error
-2. Time-out error
During inverter running
Under inverter trip
Inverter type mismatch
Inverter read lock
Instantaneous power
failure restart function
in operation
Under voltage
Power OFF
Autotuning function
end display
This is displayed when an error occurs between the inverter and remote
operator. When the STOP key or another key is pressed, the original display
appears. When the original display does not appear, turn the power off and
then on once again. Check whether any connectors are loose.
If one of the displays on the left occurs when the copy unit is used to read or
copy, take the corresponding countermeasure.
INV. RUN : Stop the running.
INV. TRIP : Press the STOP key to release the trip.
INV. TYPE : The inverter type of the copy source is different from that of
the copy destination.
Use the same type of inverter to read or copy.
The fourth switch of the DIP switch on the back of the remote operator is ON.
When reading data, turn the switch OFF.
This indicates that the instantaneous power failure restart function is being
performed.
RESTART : 0 start is in execution
ADJUST : Frequency matching is in execution.
The supply voltage is lowered to the undervoltage level.
When this display appears, turn the power on once again
The undervoltage after the power is turned off is displayed.
This is displayed after the autotuning measurement is finished.
Tuning OK : The measurement terminates normally.
Tuning NG : The measurement fails.
E 60
E 6 1
E 62
E 64
E 65
E 67
NOTE 1 : When the J-FB is installed, and error is display for each factor as shown below.
OP1 0
OP1 1
OP1 2
OP1 4
OP1 5
OP1 7
Digital operator
display
Encoder line break :
Overspeed :
Positioning error :
Thermistor line break :
Motor overheat :
Malfunction or abnormality on built-in CPU of the option :
DOP, DRW
Summary of Contents for J300 series
Page 1: ......
Page 74: ...J3005 INSTRUCTION MANUAL HHIS WZ PE 002 02 ...
Page 88: ...J3005 INSTRUCTION MANUAL 11 STANDARD SPECIFICATIONS ...
Page 89: ...J3005 INSTRUCTION MANUAL ...
Page 131: ...J3005 INSTRUCTION MANUAL Appendix 5 Multi Motor Operation and Precautions for Operation ...
Page 132: ...J3005 INSTRUCTION MANUAL ...
Page 133: ...J3005 INSTRUCTION MANUAL ...