Leakage / Drainage - 1/5
Case-5
Factor
Water leaks caused by the inclined indoor unit and the drain hose's bad connecting.
1. Indoors leveling
2. Drain hose connecting.
Troubles &
Causes
Defect Details
Guidelines
■
Indoors need to be leveled.
(For a better drain the install-plate may be
tilted 2~3° to drain-pan's drain side)
Install-plate
Weight
■
Confirm the water draining is good or not by
poring water into the drain pan.
■
Connecting parts of drain pan and hose should
be well fixed with bond for waterproofing.
2. Mal-linked drain hose
1. Non-leveled indoor
Horizon
Evaporator
Drain pan
Connect hoses with drain pan
drainage
leaks
Slanted
Air Conditioner Service Manual
85