3-5
S
ETUP
Operator Manual
Input
Phase
Input
Recommended Power Cord Wire Size (mm
2
)
Voltage
Current
< 3 m
3 – 7.5 m
7.5 – 15 m
15 – 30 m
30 – 45 m
200 VAC
1
96A
25
25
25
35
35
230 VAC
1
84A
25
25
25
25
35
400 VAC
1
48A
10
10
10
10
16
200 VAC
3
56A
10
10
16
16
16
230 VAC
3
49A
10
10
10
10
16
400 VAC
3
28A
4
4
4
6
6
5" (140 mm)
7.5" (178 mm)
Ground
L1
L2
L3
Input
Phase
Input
Recommended Power Cord Wire Size (AWG)
Voltage
Current
< 10 ft
10 – 25 ft
25 – 50 ft
50 – 100 ft
100 – 150 ft
208 VAC
1
92A
4
4
4
2
2
240 VAC
1
80A
6
6
4
4
4
480 VAC
1
40A
8
8
8
8
6
208 VAC
3
53A
6
6
6
6
4
240 VAC
3
46A
8
8
8
6
6
480 VAC
3
23A
10
10
10
10
8
Figure 3-6 Power Cord Stripping for 208/240/480V and 200/230/400V Power Supplies
POWER CORDS - 208/240/480V, 200/230/400V and 600V POWER SUPPLIES
The 208/240/480V and 200/230/400V power supplies are shipped without a power cord. Use the tables
below to choose the proper wire size for the appropriate length cord. In the U.S., use a 3-conductor SO
type cord for single-phase, and a 4-conductor SO type cord for three-phase power supplies. In other
countries, use cords that are certified by local or national codes. Strip the power cord wires as shown in
Fig. 3-6. Cap or tin the conductor leads and use a #10 terminal on the ground wire. The cord should be
installed only by a licensed electrician.
The 600V conversion kit comes with a 10 AWG 7 ft (2 m) power cord. If changing the cord length, use a
10 AWG power cord.
208/240/480V Power supplies
200/230/400V Power supplies