InstallatIon
HPR130XD Auto Gas –
806330
3-25
Notes to cNc interface cable run list
Note 1. I
nputs are optically isolated. They require 24 VDC at 7.3 mA, or dry-contact closure.
The external relay’s life
may be improved by adding a metallized-polyester capacitor (0.022µF 100 V or higher) in parallel with the
relay contacts.
Note 2.
Outputs are optically isolated, open collector, transistors. The maximum rating is 24 VDC at 10 mA.
Note 3. Machine motion is selectable and is used for configurations with multiple plasma systems.
Note 4.*
CNC +24 VDC provides 24 VDC at 200 mA maximum. A jumper is required on J301 to use 24 V power.
caution:
the cNc cable must be constructed using cable with 360 degree shielding and
metal housing connectors at each end. the shielding must be terminated to the
metal housings at each end to ensure proper grounding and to provide the best
shielding.
* See example 1 on page 3-27
Summary of Contents for HyPerformance HPR130XD
Page 1: ...HyPerformance Plasma HPR130XD Auto gas Instruction manual 806330 Revision 3 ...
Page 16: ...Table of Contents viii HPR130XD Auto Gas 806330 ...
Page 26: ...Specifications 2 2 HPR130XD Auto Gas 806330 ...
Page 38: ...Specifications 2 14 HPR130XD Auto Gas 806330 ...
Page 48: ...Installation 3 10 HPR130XD Auto Gas 806330 ...
Page 59: ...Installation HPR130XD Auto Gas 806330 3 21 1X1 J103 J300 Female Male 5 6 5 6 3X1 3X2 3X3 3X4 ...
Page 94: ...Installation 3 56 HPR130XD Auto Gas 806330 ...
Page 101: ...Operation HPR130XD Auto Gas 806330 Revision 2 4 7 Diagnostics screen ...
Page 102: ...Operation 4 8 HPR130XD Auto Gas 806330 Revision 2 Test screen ...
Page 103: ...Operation HPR130XD Auto Gas 806330 Revision 2 4 9 Cut chart screen ...
Page 152: ...Operation 4 58 HPR130XD Auto Gas 806330 Revision 2 ...
Page 236: ...7 4 HPR130XD Auto Gas 806330 Discrete output functionality ...
Page 294: ...Appendix B CNC Interface Protocol b 28 HPR130XD Auto Gas 806330 Revision 1 ...
Page 302: ...4 HPR130XD Auto Gas 806330 ...