SPA
Page 9
Touch Screen
information:
Tap in the centre of an icon to select it.
Please tou ch th e tou chscreen only lig htly. It is sen sitive e nough to
react to a gentle touch.
3.2 Operating Status LED
The operating st atus LED indi cates d ifferent o perating st ates with
different colors.
These are:
LED Color
Operating Status
light blue
Filling
(the steam cylinder is supplied with water)
white
Ready for Use
(the safety chain (clamp 1/2) is open; the device is
not enabled for steam production)
dark blue
ECO
(device operates in ECO mode)
orange
No Demand
(the requirement is below the switching-on point of
the steam generator)
green
Humidifying
(steam is produced)
green blinking
Service
message
purple
Blow-down
(cylinder water is blown-down)
flashing red
Fault
(the device is switched off with an error message
on the display)
flashing yellow
Safety Stop
Operating time equals the parameter set for
„Operating time limitation“. Operation is halted.
black
No communication