SPA
Page 15
4.4.1.2 Temperature
»
Select
Steam bath
»
Select
Temperature
Changing the temperature set value of the steam bath:
»
Select
Temperature set value
to change the set temperature
»
Select a value between 20°C and 49°C and confirm the entry
»
Quit the menu with
Adjusting the hysteresis of the temperature control:
»
Select
Hysteresis Temp.(
this parameter defines the
temperature value for cutting the steam production with
respect to the temperature set value)
»
Select a value between 0K and +10K (entry in 1K steps
possible) and confirm the entry
»
Quit the menu with
Adjusting the hysteresis for stopping steam production and gene-
rating the „Error °C Max“ alarm message
»
Select
Hysteresis Temp. max
(this parameter determines at
which temperature with respect to the temperature set value
steam generation is cut and the alarm „Error °C max“ is
generated
»
Select a value between 0K und +10K (entry in 1 K steps
possible) and confirm the entry
»
Quit the menu with
4.4.1.3 Light
»
Select
Steam bath
»
Select
Light
Light (on/off)
»
Select
On
to switch on light control or
»
Select
Off
to switch off light control
»
Quit the menu with
Light on power-up of the steam generator (on/off)
»
Select
On
for switching on light control on start-up of the
steam generator
»
Select
Off
, for swiching off light control on start-up of the
steam generator
»
Quit the menu with
Temperature
Hysteresis Temp. max
10 K
1 K
45,0 °C
Temperature set value
Hysteresis Temp.
Light
Light on power-up
Off
On
On
Off