SPA
Page 29
5. Parameters
Para-
meter
Designation
Range
Description of parameter
Menu/Sub-
menü
A4
Stand-by blow-
down
0H0:00 to
600:00
[HH:MM]
factory setting =
24:00
In case of interruption of the steam bath gener-
ator by means of the security chain expectedly
for a longer period of time while the main power
switch remains in the on-position, it is advisable
to blow-down the cylinder filling. Parameter A4
(Stand-by blow-down) determines the period of
time after which a full blow-down is initiated
automatically. Only when the security chain is
closed again while a demand is identified,
water is fed to to the cylinder again.
Operator menu/
Blow-down
A 17
Stand-by heating/
temperature pres-
ervation
on = stand-by
heating
off =tempera-
ture preservation
factory setting =
off
If stand-by heating is selected the normal
steam production operation is cut. However,
the main contactor is switched on and off peri-
odically as determined by the heating time
(parameter C17), thus heating-up the water in
the cylinder. Heating-up is followed by a pause
as determined by the interval time parameter
C16, and so on.
Standby-heating is only operational in ECO
mode when A17 = on. On A17 = off, tempera-
ture preservation is operational, i.e. the steam
bath temperature is held on a lower set value
(as determined by E11).
ECO/Settings
C17
Heating time
0 - 255 s
factory setting =
15 s
see parameter A17 (stand-by heating)
ECO/Settings/
Stand-by heat-
ing
C16
Pause time
0 - 255 min
factory setting =
25 min
see parameter A17 (stand-by heating)
ECO/Settings/
Stand-by heat-
ing
D1
Exhaust fan
off/permanently
on/automatic
factory setting =
automatic
When set to automatic mode the fan is
switched on depending on (G2 + G3)
Steam bath/
Fan/Exhaust fan
D2
Essence
on/off
factory setting =
on
Intensity is determined by E14
Steam bath/
Essence
D3
Light
on/off
factory setting =
off
Light is switched on on power-up of the steam
generator. Additionally, direct light on/off is
availabel as determined by an internal parame-
ter.
Steam bath/
Light
D4
Supply fan
off/Permanently
on/Automatik
factory setting =
automatic
When set to automatic mode the fan is
switched on depending on (G2 + G13)
Steam bath/
Fan/Supply fan
D5
Operating time
limitation
0 - 255 h
factory setting =
8
maximum operating time of the steam genera-
tor before automatic cut-off occurs
Operator menu/
Operating para-
meters/Operat-
ing time lim.