Page 18
Guidelines for water discharge composi-
tion
•
Use flexible water hose
•
Do not buckle drain hose
•
Discharge line and drain pipe material
must be temperature resistant up to
95°C (203 °F)
How to proceed
»
Run a 1 1/4 " drain hose of 250 to
1000 mm (10 to 40 inch) length into
a pressure-free outlet according to
DIN EN 1717. The hose must be
guided sideways of the humidifier to
prevent ascending vapor from con-
densating on the humidifier`s
housing.
»
Fit drain hose to connection stub on
humidifier housing bottom side.
Grounding clip functioning
The two grounding clips attached to the inner
surface of the housing drain stub are in direct
contact with water and shunt potential resi-
dual electric currents away from the housing
during blow-down and in case of a cylinder
water overflow.
With the optional wastewater cooling system
HyCool
, HygroMatik offers an option for limi-
ting the steam humidifier wastewater temper-
ature in order to protect thermosensitive
wastewater pipe lines. By blending with tap
water during blow-down and rinse pro-
cesses, wastewater temperature is below
60 °C (140 °F) as long as inlet water temper-
ature does not exceed 30 °C (86 °F).
7.4 Water connections final
check
Go down the following water installation
checklist:
All screws and clamps properly tigh-
tened?
Water supply line flushed before
making connections?
Water connection properly installed?
Water discharge properly installed?
Does blow-down water drain freely?
Water supply line and water
discharge leakage-free?
Drain hose from pump
Grounding clips
Drain stub on
housng