Page 56
Read values continued
57 Pressure_set_value
The set point of the system pressure in bar
60 Frequency_set_value
The frequency set value for the frequency inverter
61 Load_actual
The current load situation in the spray system
0
The spraying system is not in operation
1
The spraying system works in single load mode
2
The spraying system works in two-load mode
3
The spraying system works in three-load operation
4
The spraying system operates in four-load mode
5
The spray system works in the operating mode exhaust air cooling.
10
The pressure in the spray system is reduced before the humidification is switched
off
11
The pressure relief is started
12
Pressure relief is underway
20
The pressure in the spraying system is reduced before a load switch is performed
21
Switching between 2 load ranges takes place only after a waiting time (see
param. 15/8) in order to counteract an oscillation tendency
22
The plant system is in the phase of switching between 2 load ranges
23
The spraying system waits for the opening of the water inlet solenoid valve, which
may be delayed due to pressure situation
24
The system checks whether flushing of the humidification nozzle sections is
necessary
25
The system checks whether flushing of the cooling nozzle section is necessary
30
The flushing of the humidification nozzle sections is in progress
31
Flushing of the cooling nozzle section is in progress (only for combined systems)
32
A hygiene flush is underway
33
The flushing of the humidification lines and the cooling line is in progress (only for
combination systems)
99
The switching points for load changeover are not set correctly.
62 Solenoid_valve_flush
Status of the flushing solenoid valve
0 closed
1 open
63 Solenoid_valve_inlet
Inlet solenoid valve status
0 closed
1 open
64 Loadstage
1
Status of the solenoid valve for switching the first load (at ST04 11)
0 closed
1 open
65 Loadstage
2
Status of the solenoid valve for switching the second load (at ST06 11)
0 closed
1 open
66 Loadstage
3
Status of the solenoid valve for switching the third load (on ST02-A 9)
0 closed
1 open
67 Loadstage
4
Status of the solenoid valve for switching the fourth load (on ST10.1 20)
0 closed
1 open
68 Cooling
Status of solenoid valve for switching cooling (at ST10.1 20)
0 closed
1 open
69 Unit_total_runtime
The total runtime of the unit since its first connection to the power supply
(specified in days/months/years/hours/minutes)
1st_load
2_Load
3_Load
4_Load
Cooling
Switchover_off_pressure_max
Read value
Read value
Read value
Off
Flush_cooling_check
Flush_humidification_check
Flush_humidification
Flush_cooling
Flush_hygiene
Flushing_humidification_cooling
Discharge_start
Discharge
Switchover_pressure_max
Switchover_waiting
Switchover
Wait_inlet_valve
On
Read value
Off
On
Read value
Off
Error_steps
Read value
Off
On
Read value
Off
On
Read value
Off
On
Read value
On
Read value
Off
On
Read value
Off