Tone number

 

Alternative tone pattern description

 

DIP switches

 

0

 

970Hz continuous

 

11111

 

1

 

800Hz continuous

 

11101

 

2

 

1000Hz continuous tone

 

01011

 

3

 

500

-

1200Hz for 3500ms, then off for 500ms

 

10101

 

4

 

800Hz continuous

 

00111

 

5

 

2400Hz continuous

 

10010

 

6

 

800Hz continuous

 

11110

 

7

 

500Hz continuous

 

11100

 

8

 

500Hz continuous

 

10100

 

9

 

2400Hz continuous

 

10001

 

10

 

500

-

1200Hz sweep for 3750ms, then OFF for 250ms

 

10110

 

11

 

500

-

1200Hz rising for 250ms, then falling for 250ms

 

00001

 

12

 

800Hz continuous

 

00101

 

13

 

2800Hz continuous

 

11011

 

14

 

800Hz continuous

 

11001

 

15

 

2800Hz continuous

 

01001

 

16

 

800Hz continuous

 

01111

 

17

 

800Hz continuous

 

01101

 

18

 

970Hz for 500ms, then OFF for 500ms

 

01110

 

19

 

2850Hz for 500ms, then OFF for 500ms

 

01100

 

20

 

800Hz continuous

 

11010

 

21

 

800Hz continuous

 

01010

 

22

 

800Hz continuous

 

11000

 

23

 

800Hz continuous

 

00000

 

24

 

800Hz continuous

 

00010

 

25

 

660Hz continuous

 

00100

 

26

 

660Hz for 150ms, then OFF for 150ms

 

00110

 

27

 

800Hz continuous

 

10111

 

28

 

800Hz continuous

 

10011

 

29

 

800Hz continuous

 

01000

 

30

 

2900Hz continuous

 

00011

 

31

 

800Hz continuous

 

10000

 

Table 6

 

www.hyfirewireless.com

 

Hyfire Wireless Fire Solutions Ltd 

-

 Unit B12a, Holly Farm Business Park, Honiley, Warwick-

shire, CV8 1NP 

-

 United Kingdom

 

 

10

 

Summary of Contents for TAURUS TAU-BS-01-BL

Page 1: ...ice and other internationally recognized fire engineering stand ards Appropriate risk assessment should be carried out initially to determine correct design criteria and updated periodically Use only in Taurus fire detection and alarm systems WARRANTY All devices are supplied with the benefit of a limited 5 years warranty relating to faulty materials or manufacturing defects effective from the pro...

Page 2: ...te TAU BS 01 BL and TAU BSB 23W 01 BL are battery powered and they don t need any system cabling installation Picture 1 Battery A lodgement Battery B lodgement LED indicator Output selection DIP switch Link program switch Tamper switch Sound diffuser Acoustic alarm outlet www hyfirewireless com Hyfire Wireless Fire Solutions Ltd Unit B12a Holly Farm Business Park Honiley Warwickshire CV8 1NP Unite...

Page 3: ...CONFIGURATION 9 Set the output visual signal s power applicable only to TAU BSB 23W 01 BL See SOUNDER OUTPUT S CONFIGURATION 10 Drill out the required fixing holes on the wall installation plate See WALL INSTALLATION PLATE 11 Fix the wall plate See WALL INSTALLATION PLATE 12 Install the base sounder to the wall plate See WALL INSTALLATION PLATE 13 Fix the base sounder to the wall plate See FIXING ...

Page 4: ...ion quality BATTERY COVER To detach the battery cover pull the tab highlighted in the following picture To reinstall the battery cover insert its two hooks into the device s recesses as indicated in the picture below then block it by pressing down the opposite side It is advisable to use the TAU STK 01 survey kit to locate a good wireless installation location Picture 2 Picture 3 Every time the co...

Page 5: ...following picture Drill templates on the wall plate are highlighted in the following picture Make sure that the sound diffuser cone printed on the wall plate corresponds to the acoustic alarm signal outlet of the base sounder Picture 4 Picture 5 L20 TWBSXB 1400 vA 2 info hyfirewireless co uk 5 ...

Page 6: ...at the batteries are installed properly with their polarities matching the indications on the device POWERING UP RECOVERY Use this procedure when you fail to link successfully a TAU BS 01 BL or a TAU BSB 23W 01 BL or you want to link it again 1 Move alternatively the Link program switch 5 times 2 Set the Link program switch on ON 3 Insert the two supplied batteries into their device s lodgments En...

Page 7: ...uREX or from TAU TRM 01 TAU CEM 01 for linking success Consult their user manual LINKING ONE BY ONE One by one linking consists in associating one child device at a time to the Taurus system This operation is performed either through the TauREX software or the TAU TRM 01 TAU CEM 01 keyboard screen interface it CANNOT be done through TAU EXM 01 devices 1 Create the virtual model of the child device...

Page 8: ...set 3 Select the required output volume switches combinations and the corresponding volume levels are found on table 3 4 Select the visual emission s power switch settings and the corresponding power levels are found on table 4 applies only to TAU BSBS 23W 01 BL EN 54 3 approved volume Visual emission power level Switch configuration High 1 Low 0 Acoustic volume level Switches configuration High 1...

Page 9: ...p interrupted tone fast 2800Hz for 150ms then OFF for 150ms 11001 15 HF Continuous 2800Hz continuous 01001 16 Interrupted tone 800Hz for 500ms then OFF for 500ms 01111 17 Interrupted tone medium 1000Hz for 250ms then OFF for 250ms 01101 18 ISO 8201 LF BS5839 Pt 1 1988 970Hz for 500ms then OFF for 500ms 01110 19 ISO 8201 HF 2850Hz for 500ms then OFF for 500ms 01100 20 LF Back up Alarm 800Hz for 150...

Page 10: ...0Hz continuous 11011 14 800Hz continuous 11001 15 2800Hz continuous 01001 16 800Hz continuous 01111 17 800Hz continuous 01101 18 970Hz for 500ms then OFF for 500ms 01110 19 2850Hz for 500ms then OFF for 500ms 01100 20 800Hz continuous 11010 21 800Hz continuous 01010 22 800Hz continuous 11000 23 800Hz continuous 00000 24 800Hz continuous 00010 25 660Hz continuous 00100 26 660Hz for 150ms then OFF f...

Page 11: ...stallation manual For placing the detector plastic cover refer to the following picture Picture 7 Make sure the detector s OWN battery cover is installed to avoid tamper detection events If a detector is not hosted always use a Taurus cover plate to close and protect the inside of the base sounder The cover plate is not supplied together with the product Always install the safety blocking screw Pi...

Page 12: ...alarm condition call point activation approved detector aerosol heat testers 2 Check the acoustic alarm output of the base sounder 3 Check the visual alarm output of the base sounder TAU BSB 23W 01 BL only 4 Remove the alarm condition 5 Check that a normal condition persists i e test smoke can stagnate in a detector s smoke chamber causing the alarm to be triggered again When a low battery conditi...

Page 13: ...ith TAU TRM 01 TAU CEM 01 or TAU EXM 01 network devices 200 m in open space Wireless frequency band 868 MHz Number of wireless channels 66 Radiated power 14 dBm 25 mW Operating temperature range 10 C to 55 C Maximum humidity non condensing 95 RH Certified IP rating EN 54 IP 21C Environmental application Indoor use only Type A as per EN 54 3 Specification Value Batteries type CR123A 3 V 1 25 Ah TAU...

Page 14: ...ne 4 German DIN tone typical sound output 89 dB A Acoustic output frequency range 440 Hz to 2900 Hz Table 9 Table 10 Table 11 Table 12 www hyfirewireless com Hyfire Wireless Fire Solutions Ltd Unit B12a Holly Farm Business Park Honiley Warwickshire CV8 1NP United Kingdom 14 Specification Value Notes Flash frequency 0 5 Hz WHITE flash HIGH power coverage Ceiling mounted 3 m height 15 m coverage dia...

Reviews: