background image

Installation and Commissioning     5

12

ST16135-00E

5.4

Electrical Installation (Fig. 5.2)

WARNING ! 

BEFORE STARTING WORK, ENSURE THAT THE 
MAIN-LINE FUSES HAVE BEEN REMOVED FROM 
THE DISTRIBUTION BOARD. PRECAUTIONS 
SHOULD BE TAKEN TO PREVENT THEM BEING 
REFITTED UNTIL THE INSTALLATION IS 
COMPLETE.

Starter cables must be connected to the mains electrical supply 
via a lockable, switched and suitably rated fused isolator. The 
isolator should be positioned as near as possible to the 
compressor with clear, unrestricted access.

To access starter terminals, unlock the starter door panel and the 
front panel on HV30-HV45 with the key provided. Pass incoming 
cables through the entry hole in the floor for HV04-HV22 or left 
hand side panel and rear of starter panel for HV30-HV45.

Connect the three mains supply cables to the contactor terminals 
marked L1, L2 and L3, and connect the earth cable to the earth 
pin E. Ensure the connections are secure.

Fig. 5.2 - Electrical Connections to Starter 

Terminal

Cable sizes specified on the circuit diagram are the minimum size 
to suit a typical installation. If the compressor is located a long 
way from the isolator and/or the ambient temperature exceeds 
35°C, the cable size should be increased.

Refer to IEEE Regulations for electrical equipment installed in 
buildings to determine the size required, pay particular attention to 
the circuit diagrams provided.

Check that the transformer fuse is positioned to suit the supply 
voltage of the installation. 

Ensure all electrical connections are tight, high voltage supply to 
contactors and incoming terminals are critical.

Close the starter door and secure with the key provided before 
replacing the main line fuses.

5.5

Check Direction of Motor Rotation

WARNING ! 

READ HEALTH AND SAFETY PRECAUTIONS 
BEFORE STARTING COMPRESSOR.

Ensure that the compressor is filled with approved oil and that all 
plugs are fitted securely.

Refer to Section 9.6, Access Panel Removal to remove the top 
panel so that the compressor pressure gauge can be viewed.

With the mains isolator on, press the green start button mounted 
on the control panel and watch the pressure gauge.

Rotation is correct if the pressure display rises immediately, after 
a few seconds if no pressure is displayed rotation is incorrect.

WARNING ! 

IF ROTATION IS INCORRECT, STOP THE 
COMPRESSOR IMMEDIATELY. SERIOUS 
DAMAGE WILL OCCUR IF THE MOTOR IS 
ALLOWED TO RUN IN REVERSE.

ISOLATE THE ELECTRICAL SUPPLY.

Open the starter door and change over any two of the incoming 
cables connected to the starter terminals L1, L2 and L3.

Close and lock the starter door to prevent unauthorised access 
and switch the mains electricity supply on.

Restart the compressor and verify that direction of rotation is 
correct by observing pressure rise on the compressor gauge.

Replace the top panel and close and lock both front and starter 
panel doors.

Cooling fan operation is clockwise, single speed HV30-HV45 and 
all RS units have automatic stop/start cooling fans that cut in at 
85°C operating temperature.

Remove the cabinet filter from the lower half of the rear panel to 
view the cooling fan through the mesh grill.

5.6

Regulated Speed Compressor Installation

Install as instructed for standard fixed speed compressors with the 
same fuse sizes for a given power rating.

Circuit breakers (Type D) with motor starting characteristics of 
suitable size may be used to protect the installation. 

Starting currents will not exceed 150% motor full load current and 
will generally be no more than 100% full load current.

Installations must be earthed in accordance with local regulations, 
the use of RCDs is not recommended.

Water drain, filters or dryers fitted downstream of the compressor 
discharge must be correctly sited to avoid excessive flow 
restrictions to ensure stable operation of the speed control 
system.

Summary of Contents for HB18

Page 1: ...User Handbook HV04 HV45 Models ACE Stationary Air Compressors ST 16135 00 Iss E 05 2009 GB...

Page 2: ......

Page 3: ...ion 9 4 2 Lifting and Handling Fig 4 1 and Fig 4 2 9 4 3 Model Weights 9 5 Installation and Commissioning 11 5 1 Positioning Your Compressor Basic Requirements 11 5 2 Ventilation Fig 5 1 11 5 3 Electr...

Page 4: ...Oil Filter Replacement Fig 9 3 24 9 10 Oil filling Top up Fig 9 3 25 9 11 Air Filter Replacement Fig 9 2 25 9 12 Oil Separator Replacement Fig 9 2 25 9 13 Clean Oil Cooler Aftercooler Fig 9 4 25 9 14...

Page 5: ...ir com 1 5 Model Range This Handbook relates to all ACE HV04 HV45 vertical range compressors and hypac models V04ACE07 4035D400 50Hz model V04ACE10 4035D400 50Hz model V04ACE07 4035S400 50Hz model V04...

Page 6: ...el V45ACE08 2036D150 60Hzmodel V45ACE10 2036D150 60Hzmodel V45ACE08 5736D150 60Hzmodel V45ACE10 5736D150 60Hz model The last three digits of the product code represent mark number changes you may rece...

Page 7: ...he compressor s vent down cycle is complete Release any pressure contained in the aftercooler or associated pipework Check that the compressor pressure gauge reads zero Do not proceed until it does Ca...

Page 8: ...e is any suspicion of aspiration into the lungs for example during vomiting admit to hospital immediately Pressure injection Obtain immediate medical attention even if injury appears minor Spillage So...

Page 9: ...e required Conditions or applications which prevent the compressor temperature stabilising between these parameters should be avoided Single speed HV30 HV45 and all RS units have automatic stop start...

Page 10: ...or 10 5 7 5 Servo Valve bar 8 0 or 11 0 8 0 Run on Time after PU secs RT 120 60 Run on Time to Stop secs ST 2 Pressure Display Units P 0 bar 1 psi 2 kpa Temperature Display Units T 0 C 1 F Vacuum Rel...

Page 11: ...8 0 Unload Pressure bar PU 8 5 or 10 5 8 5 Servo Valve bar 9 0 or 11 0 9 0 Run on Time after PU secs RT 60 8 bar 90 10bar 60 Run on Time to Stop secs ST 2 Pressure Display Units P 0 bar 1 psi 2 kpa Te...

Page 12: ...8 5 Servo Valve bar 9 0 or 11 0 9 0 Run on Time after PU secs RT 60 8 bar 90 10bar 60 Run on Time to Stop secs ST 2 Pressure Display Units P 0 bar 1 psi 2 kpa Temperature Display Units T 0 C 1 F Vacuu...

Page 13: ...the hypac or compressor and place it in the desired location Fig 4 2 ACED HV11 22 Hypac Compressor Damage to mountings may occur if you attempt to slide the compressor into position Take care when mo...

Page 14: ......

Page 15: ...ated in a moderate ambient temperature If temperatures frequently fall below 0 C consult your Hydrovane D istributor A different grade of oil may be required Compressor air intake and exhaust grills h...

Page 16: ...that the compressor is filled with approved oil and that all plugs are fitted securely Refer to Section 9 6 Access Panel Removal to remove the top panel so that the compressor pressure gauge can be v...

Page 17: ...vane standard single speed compressors feeding a common pressure system the minimum air line pressure of the RS compressor must be limited to the lowest maximum air line pressure of the single speed m...

Page 18: ......

Page 19: ...st savings due to the offload power reduction During offload run on time at minimum pressure the compressor will either stop with no air demand or return to onload running if more air is required Auto...

Page 20: ...the oil system is filtered by an oil filter L An oil level sight glass M is mounted adjacent to the oil filter The compressor is filled and topped up with oil via the oil filler N The sight glass M w...

Page 21: ...n and red LED indicators for three seconds Fig 7 1 The display then shows the software version code for a further three seconds before showing the normal operating display Single speed compressors all...

Page 22: ...s Mode Press the green START button the compressor will start and run continuously within the load unload PL PU pressure set points to match system demand On initial start with no pressure in the syst...

Page 23: ...r Remote start stop Filter differential pressure Normal operational mode Selected item locked as temporary default display Menu mode Page item locked adjustment inhibited Pressure set point indication...

Page 24: ......

Page 25: ...mperature Display Units h 01 15 Error Log A selected item will flash press plus up or minus down button to change a value or select an alternative press ENTER to select During changes if no key activi...

Page 26: ...adjustment or a lower pressure is required then carry out the following procedure a Turn the electrical supply on at the isolator disconnect the air outlet valve from the system and fit an air silence...

Page 27: ...Distributor 9 3 Servicing RS Servicing intervals and procedures are the same as specified for the standard fixed speed compressor of the same power kW rating The speed control unit does not require an...

Page 28: ...the top panel from the snap fit location pegs or location slots and lift clear of the compressor Check that the compressor pressure gauge reads zero 9 7 Oil Draining and Filter Replacement Fig 9 2 and...

Page 29: ...g area behind the cabinet filter B All discarded items and waste oil must be disposed of in an approved manner 9 14 Cabinet Air Filter Remove the disposable filter located in the rear panel by sliding...

Page 30: ...extreme ambients HPO oil should be used at the 2000 hour oil change periods If the oil is working above these temperatures the oil life will be significantly reduced If changing to Fluid Force Clear...

Page 31: ...X X X Check motor for damage X X X X Check motor starter for loose connections X X X X Check motor cables and earth X X X X Check motor for vibration X X X X Check flexible oil pipes X Check oil seal...

Page 32: ...otor for damage X X X Check motor starter for loose connections X X X Check motor cables and earth X X X Check motor for vibration X X X Check flexible oil pipes X Check oil seal for leakage X Check d...

Page 33: ...low General fault Emergency stop Excess pressure Power failure Above set temperature limit Lubrication oil oil level Dewpoint Motor Service due maintenance Filter differential filter service Er 0010 E...

Page 34: ...enu P21 For authorised engineers to install or service compressors as part of an approved installation or maintenance program 10 10 Diagnostic Menu P22 Allows an authorised technician to check and tes...

Page 35: ......

Page 36: ...ion of the Technical Publications Department Gardner Denver Ltd Gardner Denver Ltd Claybrook Drive Washford Industrial Estate Redditch Worcestershire B98 ODS United Kingdom Tel 44 0 1527 525522 Fax 44...

Reviews: