![HydroTherm KN-2 Installation Instructions Manual Download Page 21](http://html1.mh-extra.com/html/hydrotherm/kn-2/kn-2_installation-instructions-manual_2192580021.webp)
P/N 42-9540 11/12 Copyright 2012 Hydrotherm
Page 21
KN INSTALLATION INSTRUCTIONS FOR VENT AND AIR PIPING
Vent and air piped through a side wall
(separate terminations)
5
Figure 15
Termination minimum clearances
7 — Sidewall termination assemblies
(see Figure 15)
❑
See Table 5 for part numbers of the sidewall termination components required for
EZ-Seal vent pipe installations. Th e vent termination must be constructed using
the stainless steel vent materials listed in Table 5 to ensure the confi guration is
correct. DO NOT terminate the air piping with any other method.
A.
Wall thimble
— Use only the thimble listed in Table 5. Th e hole in the
thimble will prevent the pipe length (
B
) from being pushed inward. Th e
raised portion of the pipe female end is too large to pass through the hole in
the thimble. Follow the vent pipe manufacturer’s instructions supplied with
the thimble. If the wall thimble isn’t long enough for the application, follow the
vent manufacturer’s instructions to add an extension.
Noncombustible walls
— For noncombustible walls ONLY, you can omit
the thimble. For this option,
attach a storm collar on both the inside and
outside walls at the penetration
. Before att aching the collars, seal around
the vent pipe thoroughly with silicone RTV to prevent air leakage or insect
access. Th e storm collar tightens around the vent pipe with a gear clamp. Th is
prevents movement of the fi nished assembly. You will still need to use the
length of vent pipe and the termination elbow described below.
Air intake termination alternate construction
— Air pipe terminations
can be installed without thimbles through all walls, whether combustible or
noncombustible. Th e termination assemblies
must use storm collars
as
described above for vent piping through noncombustible walls.
B. Length of vent pipe
— Use a 1-foot length of vent pipe as listed in Table 5
unless the wall penetration quires a longer length. If a longer length is required,
use a length of EZ-Seal long enough for the application.
Insert the pipe from OUTSIDE, male end fi rst. Th e pipe will stop at the raised
section of the female end.
C. Gear
clamp
— Use a hose clamp or a gear clamp manufactured by the vent
manufacturer (see Table 5).
Slide the clamp over the male end of the pipe aft er the pipe has been inserted
from outside.
From the inside, pull the pipe so it is fi rmly against the outside plate.
Push the gear clamp against the inside plate and tighten securely. Th is will
prevent the termination assembly from being pushed outward.
D. Termination elbows
— Use only the termination elbows listed in Table 5.
Th e elbows must be pointed downward.
Before inserting the male end of the elbow into the pipe, apply a bead of
silicone RTV and spread around the end.
Insert the termination elbow and secure using the vent pipe manufacturer’s
joint assembly procedure.
Termination location — Install the vent pipe termination where it meets the
minimum clearances shown in Figure 16 and minimum spacing to air intakes
as shown in Figure 18.
Exiting below grade or snow line
— See Figure 17. When the vent pipe
must exit the building below grade or below the minimum height for the
termination elbow, install vertical piping as necessary for the termination
elbow to be high enough to meet the minimum clearances of Figure 16. Make
sure to support the piping using wall brackets available from the vent pipe
manufacturer.
If the vent pipe extends more than 3 feet
(0.9 m)
, insulate the external portion
of the pipe and fi tt ings with at least 1/2-inch closed-cell foam polyolefi n pipe
insulation. Air pipes do not have to be insulated.
❑
Spacing between vent and air terminations
— Place
all vent and air terminations so they meet the clearances
shown in Figure 17. requires a longer length. If a longer
length is required, use a length of EZ-Seal long enough for
the application.
Multiple boiler installations
❑
Install multiple vent and air terminations through the side
wall following all guidelines for single-vent/air installations.
❑
Install the terminations so they are no closer than 12 inches
(305 mm)
on centers and all terminations comply with
minimum clearances shown in Figure 16 and Figure 18.
❑
See Figure 18 for relative placement of vent and air terminals
to ensure suffi cient clearance.