TROUBLESHOOTING
HeatNet Control V3 2.x
Page 89
seconds (10 minutes) to the setpoint timer. If after 10
minutes (5 minutes longer than the normal write
interval) the BMS has not written the timer, the saved
setpoint values will be restored.
2.
As a convenience, the
SETPOINT TIMER
is
automatically loaded with 60 seconds (if it has fallen
below 60) each time the setpoint is written. If you
decide to take advantage of this convenience, you
would need to write the setpoint periodically at less
than 1 minute intervals.
3.
Newer firmware versions allow the
SETPOINT
TIMER
failsafe feature to be disabled by writing a zero
(0) to the timer. The feature will automatically revert
back to the enabled state whenever the control is reset
or power cycled. The
SETPOINT TIMER
failsafe
feature can permanently disabled (or enabled) in
firmware versions
3.35
or greater. This setting can be
changed in the
ADVANCED SETUP-
>COMMUNICATIONS
menu.