FEATURES & SPECIFICATIONS
HeatNet Control V3 2.x
Page 8
Specifications
Control
Microprocessor based PID modulating control (
NOT a safety limit
)
Environment
-40 °F to 140 °F, <90% RH non-condensing
Input Power
24 VAC, 500 ma
Relays
System Pump, Damper, Circulator, Alarm, DHW Pump (v2.x), 8A 250 VAC resistive
K8 on J4.2 &.6 for Base Loading version 2.x Control
AC Interlocks
24 VAC – 120 VAC input
Control Inputs
AA, Heat Demand, 4-20ma Enable, OA override, T1-T2 (dry contact inputs)
4-20mA, 0-10 VDC
Dimensions
9‖ wide: 6‖ high : 2‖ deep
Temperature Sensors
NTC thermistor, 10K @ 77 °F, 335.67K @ -40 °F, 185 @ 150 °F ,+/- 1
F
USB
1.0
RS485 MODBUS
Modbus RTU
Boiler-to-Boiler
HeatNet (H-Net)
Network
Optional LonWorks, BACnet available bridge to MODBUS port