DELTA TEMPERATURE WARNING:
If the temperature difference across the boiler and
measured from RETURN water to SUPPLY water
exceeds ―EXCHGR DELTA‖ this message will be
displayed. This can be set to an alarm condition in the
AUX FUNCTIONS menu. High delta temperatures can
result in damage to the boiler.
BLOWER, RPM HIGH: (Ametek Blower)
If the signal from the HeatNet control board to the
Ametek blower exceeds the factory limits, or the blower
―runs away‖ (excessive speed), this message will be
displayed. With this event, the HeatNet control will
lockout the boiler and the boiler will require a manual
reset to restart. Operation of the blower above the boiler‘s
maximum blower rpm setting could over fire the boiler.
BLOWER, RPM HIGH
FAULT
HIGH FIRE
TACH
0