background image

3

INSTALLATION AND OPERATING INSTRUCTIONS

A.  ACCESSIBILITY CLEARANCES

Install boiler not less than 24

(610 mm) between the left

side, top, and front of the boiler and adjacent wall or
other appliance, when access is required for servicing.

B.   CLEARANCE FROM COMBUSTIBLE 

      CONSTRUCTION

The design of this boiler is certified for alcove installation
with the following clearances:

1. 6

″ 

(152 mm) between sides and combustible

construction.

2. 24

″ 

(610 mm) between top of jacket and

combustible construction.

3. 6

″ 

(152 mm) between draft hood and combustible

construction.

4. 6

″ 

(152 mm) between vent pipe and combustible

construction.

5. 10

″ 

(254 mm) between rear of jacket and

combustible construction.

1. PREINSTALLATION

Read carefully, study these instructions before beginning work.

This boiler must be installed by a qualified contractor.

The boiler warranty can be voided if the boiler is not installed, maintained and serviced correctly.

The equipment must be installed in accordance with those installation requirements of the authority having 
jurisdiction or, in the absence of such requirements, to the current edition of the 

National Fuel Gas Code, ANSI

Z223.1/NFPA 54 and/or CAN/CSA B149.1, 

Natural Gas and Propane Installation Code.

Where required by the authority having jurisdiction, the installation must conform to 

American Society of

Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers, ASME CSD-1.

NOTICE

In accordance with Section 325 (f) (3) of the Energy Policy and Conservation Act, this boiler is equipped with a
feature that saves energy by reducing the boiler water temperature as the heating load decreases. This feature is
equipped with an override which is provided primarily to permit the use of an external energy management
system that serves the same function. 

THIS OVERRIDE MUST NOT BE USED UNLESS AT LEAST ONE OF THE FOLLOWING CONDITIONS IS TRUE: 

•  An external energy management system is installed that reduces the boiler water temperature as the

heating load decreases.

•  This boiler is not used for any space heating. 

•  This boiler is part of a modular or multiple boiler system having a total input of 300,000 

BTU/hr or greater. 

•  This boiler is equipped with a tankless coil.

IMPORTANT

Do not install this boiler on carpeting. Boiler
installation on carpeting is a fire hazard. Install this
boiler on non-combustible flooring or use a
combustible floor pan to install this boiler on other
non-carpeted flooring.

WARNING

Do not install this boiler on combustible flooring
unless it is installed on a special combustible floor
pan. Boiler installation on combustible flooring
without the special pan is a fire hazard.

To order combustible floor pan, use the 5-digit stock
codes listed in Table 11.1 of this manual.

WARNING

Summary of Contents for 70-195

Page 1: ...er resulting in possible severe personal injury death or substantial property damage The boiler can only be operated with a dust freeairsupply Followtheinstructionmanualprocedurestoductairtotheboilera...

Page 2: ...28 A GENERAL 29 B DAILY WITH BOILER IN USE 29 C WEEKLY WITH BOILER IN USE 29 D MONTHLY WITH BOILER IN USE 29 E ANNUALLY BEFORE START OF HEATING SEASON 29 10 BOILER DIMENSIONS RATINGS 31 11 REPAIR PART...

Page 3: ...on must conform to American Society of Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers ASME CSD 1 NOTICE In accordance with Section 325 f 3 of the Ener...

Page 4: ...imum required volume of indoor air for appliances other than fan assisted and for the boiler shall be determined as follows where Iother Input of appliances other than fan assisted in Btu hr ACH air c...

Page 5: ...ucts each opening shall have a minimum free area of 1 in2 per 2000 Btu hr 22 cm2 per 2000 W of total rated input for all appliances in the space See Figure 1 5 b One Permanent Opening Method Provide o...

Page 6: ...area specified ii Where the free area through a louver or grille is not known it shall be assumed that wooden louvers will have 25 free area and metal louvers and grilles will have 75 free area iii N...

Page 7: ...N 1 Size the supply and return to suit the system A typical piping arrangement is shown in Figure 3 1 Refer also to the I B R Guide Residential Hydronic Heating Installation Design for additional guid...

Page 8: ...ler water during the cooling cycle 8 If this boiler is installed above radiation level provide a low water cutoff device either as a part of the boiler or at the time of boiler installation B SAFETY R...

Page 9: ...ves Figure 3 6 Zone Piping with Circulators C PIPING FOR ZONED SYSTEMS 1 See Figures 3 5 and 3 6 for basic zoned system layouts 2 Run each zone pipe down then up to zone to prevent air accumulation in...

Page 10: ...PROTECTION For new or existing systems that must be freeze protected 1 Glycol in hydronic applications is specially formulated for this purpose It includes inhibitors which prevent the glycol from at...

Page 11: ...to the round draft hood outlet vent connector on top of the boiler or in vent piping close to the boiler See the Vent Damper Installation Instructions below B VENT DAMPER INSTALLATION GENERAL 1 Do not...

Page 12: ...cts such as tools equipment rags etc and remove if present 5 Insert vent pipe into but not beyond the inside wall of the chimney flue 6 Do not connect vent connectors serving appliances vented by natu...

Page 13: ...ace in operation the appliance being inspected Follow the lighting instructions Adjust thermostat so appliance will operate continuously Mettre en service l appareil inspecter Suivre les instructions...

Page 14: ...e combination gas controls If your code requires such a valve a suggested location is shown in Figure 5 1 7 Check piping for leaks Use an approved gas detector a non corrosive leak detection fluid or...

Page 15: ...140 56 1 6 175 70 2 0 195 78 2 2 Pipe Length in Feet Me ters 3 4 Pipe 1 Pipe 1 1 4 Pipe 1 1 2 Pipe 10 3 0 278 7 9 520 14 7 1050 29 7 1600 45 3 20 6 1 190 5 4 350 9 9 730 20 7 1100 31 1 30 9 1 152 4 3...

Page 16: ...on of the various controls 3 This boiler is supplied with safety devices in addition to the limit For a description of these devices and how they work to ensure the safe operation of the boiler see Se...

Page 17: ...17 INSTALLATION AND OPERATING INSTRUCTIONS Figure 6 2 Wiring Diagram Intermittent Ignition 7600B Control...

Page 18: ...18 INSTALLATION AND OPERATING INSTRUCTIONS Figure 6 3 Wiring Diagram Intermittent Ignition 3200 Control...

Page 19: ...19 INSTALLATION AND OPERATING INSTRUCTIONS D SEQUENCE OF OPERATION Figure 6 4 Intermittent Ignition System Operating Sequence...

Page 20: ...r leaks If leaks are found drain the system and repair as required 8 Connect a manometer to the gas valve on the valve outlet gas manifold Use the 1 8 NPT tapping provided 9 Confirm that the gas suppl...

Page 21: ...21 INSTALLATION AND OPERATING INSTRUCTIONS Figure 7 3 Operating Instructions...

Page 22: ...22 INSTALLATION AND OPERATING INSTRUCTIONS Figure 7 4 Operating Instructions...

Page 23: ...r level is above the control s sensing well 4 LOW WATER CUT OFF FOR GRAVITY SYSTEMS OR HOT WATER BOILERS INSTALLED ABOVE RADIATION LEVEL If limit control does not incorporate a low water cut off featu...

Page 24: ...lve will weep or open allowing fresh water to enter the system 6 Do not allow the system controls to subject the boiler to excessively low water temperatures which would cause condensation of flue gas...

Page 25: ...e technicians These individuals must follow all applicable codes and regulations in repair of any boiler problems Should overheating occur or the gas supply fail to shut off do not turn off or disconn...

Page 26: ...ply ventilation and venting system 1 Insufficient pilot flame 2 Pilot burner orifice clogged 3 Overfiring 4 Misaligned burners or pilot 5 Draft problem in boiler room Delayed ignition 1 Increase pilot...

Page 27: ...IF CONTROL GOES INTO LOCKOUT OR RETRY DELAY RESET THE CALL FOR HEAT CHECK CONTINUITY OF IGNITION CABLE AND GROUND WIRE CLEAN FLAME ROD CHECK ELECTRICAL CONNECTIONS BETWEEN FLAME ROD AND MODULE CHECK F...

Page 28: ...ry Measures Provide adequate ventilation Wear a NIOSH MSHA approved respirator Wear long sleeved loose fitting clothing and gloves to prevent skin contact Wear eye goggles Minimize airborne dust prior...

Page 29: ...ound on the top of the safety relief valve see Figure 5 for location of the safety relief valve Boiler temperature should never be higher than 250 F 121 C 4 Check for water leaks in boiler and system...

Page 30: ...l to prevent leakage of the products of combustion h Re install the top of the jacket vent damper and vent pipe i Re install burners 2 Inspect entire venting system for corrosion support and joint int...

Page 31: ...r Size Jacket Rear of Jacket to c l of Vent D Left of Jacket to c l of Vent E Vent Size Diame ter F Length Depth A Width B Height C inch mm inch mm inch mm inch mm inch mm inch mm 70 26 5 8 676 12 1 2...

Page 32: ...r Pan Description Quantity Required Stock Code 1 Base Assembly 70 7800 Base Assembly 105 7801 Base Assembly 140 7802 Base Assembly 175 7803 Base Assembly 195 7804 2 Observation Cover Door 51771 3 Base...

Page 33: ...33 INSTALLATION AND OPERATING INSTRUCTIONS Figure 11 2 Manifold Figure 11 3 Gas Valve and Pilot Intermittent Ignition...

Page 34: ...6 50894 Orifice Spud 48 Natural Gas 140 8 50894 Orifice Spud 48 Natural Gas 175 10 50894 Orifice Spud 49 Natural Gas 195 12 50895 Orifice Spud 56 LP Gas 70 4 50899 Orifice Spud 56 LP Gas 105 6 50899 O...

Page 35: ...35 INSTALLATION AND OPERATING INSTRUCTIONS Figure 11 4 Block Draft Hood Figure 11 5 Jacket...

Page 36: ...or Draft Hood 140 90512 Flue Collector Draft Hood 175 90513 Flue Collector Draft Hood 195 90514 14 Flue Collector Blanket Seal specify length needed 50866 16 Jacket Assembly Complete Jacket 70 90445 J...

Page 37: ...37 INSTALLATION AND OPERATING INSTRUCTIONS Figure 11 6 Controls Circulator Vent Damper...

Page 38: ...ckett 7600P06B 50339 Limit w Sensor Hydrolevel 3200 50334 Well Hydrolevel 48 201 50723 24 Temperature Pressure Gauge 51324 25 Safety Relief Valve 30 PSI Conbraco 10 408 05 50501 Safety Relief Valve 50...

Page 39: ...39 INSTALLATION AND OPERATING INSTRUCTIONS...

Page 40: ...s been altered or modified in any way b to any expenses including labor or material incurred during removal or reinstallation of the Product or parts thereof c to any other cast iron parts of the boil...

Reviews: