INSTALLATION AND OPERATING INSTRUCTIONS
Table 5.4: Pipe Capacity
Capacity of pipe of different diameters and lengths in cubic feet
per hour [cubic meter per hour] with a pressure drop of 0.3
inches of water (75 Pa) and specific gravity of 0.60. No al-
lowance for an ordinary number of fittings is required.
Table 5.1: Natural Gas
Table 5.2: LP Gas
Size
Input
Cubic Feet / Hour
Cubic Meters / Hour
70
70
2.0
105
105
3.0
140
140
4.0
175
175
5.0
195
195
5.5
Size
Input
Cubic Feet / Hour
Cubic Meters / Hour
70
28
0.8
105
42
1.2
140
56
1.6
175
70
2.0
195
78
2.2
Pipe
Length in
Feet [Me-
ters]
3/4"
Pipe
1"
Pipe
1-1/4"
Pipe
1-1/2"
Pipe
10 [3.0]
278 [7.9] 520 [14.7] 1050 [29.7]
1600 [45.3]
20 [6.1]
190 [5.4]
350 [9.9]
730 [20.7]
1100 [31.1]
30 [9.1]
152 [4.3]
285 [8.1]
590 [16.7]
890 [25.2]
40 [12.2]
130 [3.7]
245 [6.9]
500 [14.2]
760 [21.5]
50 [15.2]
115 [3.3]
215 [6.1]
440 [12.5]
670 [19.0]
60 [18.3]
105 [3.0]
195 [5.5]
400 [11.3]
610 [17.3]
Maximum Capacity Correction Factors for
Specific Gravity other than 0.60.
Specific Gravity
0.50 0.55 0.60 0.65 0.70 0.75
Correction Factor
1.10
1.04
1.00
0.96
0.93
0.90
Specific Gravity
0.80 0.85 0.90 1.00 1.10 1.20
Correction Factor
0.87
0.84
0.82
0.78
0.74
0.71
Specific Gravity
1.30 1.40 1.50 1.60 1.70 1.80
Correction Factor
0.68
0.66
0.63
0.61
0.59
0.58
Summary of Contents for 70-195
Page 21: ...21 INSTALLATION AND OPERATING INSTRUCTIONS Figure 7 3 Operating Instructions...
Page 22: ...22 INSTALLATION AND OPERATING INSTRUCTIONS Figure 7 4 Operating Instructions...
Page 35: ...35 INSTALLATION AND OPERATING INSTRUCTIONS Figure 11 4 Block Draft Hood Figure 11 5 Jacket...
Page 37: ...37 INSTALLATION AND OPERATING INSTRUCTIONS Figure 11 6 Controls Circulator Vent Damper...