Hydromatic S4LRC Installation And Service Manual Download Page 8

8

impeller,  apply  force  then  tap
on end of socket bolt to break
impeller  loose  from  taper
shaft.

6.   Remove  key  and  pry  on  each

side  of  shoulder  of  shaft
sleeve to remove. Seal should
come off with sleeve. If sleeve
is not free, leave in place and
push  off  when  seal  plate
is removed.

7.   To remove seal plate take out

socket  head  flat  screws  and
using  screws  in  back-off 
holes,  pry  plate  loose.  This
will  also  force  seal  off  if  not
already removed. 

8.   Remove  snap  ring  that  holds

upper  seal.  Pull  seal  if  it  is
free.  If  not  free,  it  can  be
forced  off  when  shaft  is
removed.

9.   Remove  4  bolts  that  hold

bearing housing  in  place  (on
units  built  prior  to  2/14/78).
Set  assembly

in  upright

position  and  bump  end  of
shaft on hardwood block. This
will push the bearing from  the
housing  and  will  force  upper
seal from shaft.

10. Use  bearing  puller  to  remove 

bearings.  Replace  with  new 
bear ings.  Press  only  on  inner
face 

of 

bearing 

when

replacing. Pressing  on  outer
face  can  damage  the  bearing.
Bearings  are  standard  size
that  can  be  obtained  from
any  bearing  supply house  or
can 

be 

obtained 

from

Hydromatic factory.

11.

IMPORTANT:  Do  not  use
any  of  the  old  seal  parts.
Replace with all new seals.

12. Thoroughly  clean  all  castings

before  replacing  seals.  One

grain  of  dirt  between  the  seal
faces can cause failure.

13. Examine all O-rings for nicks

before using.

14. Be  sure  key  is  in  place  in

notch  of  shaft  sleeve  to
prevent sleeve from turning.

15. Use  Locktite

®

on  socket  head

locking screw in end of shaft.

16. Before refilling chamber with

oil, air test as described above.

17. Refill  both  chambers  with  oil

as described above.

18. Always  check  all  leads  with

high  voltage  or  with  Megger
for  grounds  before  operating
the pump.

Below is a list of common problems
and the probable causes:

 

WARNINg:  Before  handling
pumps  and  controls  always 
disconnect  power  first.  Do 
not  smoke  or  use  sparkable 
electrical  devices  or  flame  in  a
septic  (gaseous)  or  possible 
septic sump.

Pump will not start.
1.  No power to the motor. Check

for  blown  fuse  or  open 
circuit breaker.

2.  Selector  switch  may  be  in  the

Off position.

3.  Control  circuit  transformer

fuse may be blown.

4.  Overload heater on starter may

be tripped. Push to reset.

Pump will not start and 
overload heaters trip.

1.  Turn  off  power  and  check

motor  leads  with  Megger  or
ohmmeter for possible ground.

2.  Check  resistance  of  motor

windings. All  3  phases  should
show the same reading.

3.  If  no  grounds  exist  and  the

motor  windings  check  OK,
remove  pump  from  sump 
and  check  for  clogged  or
blocked impeller.

Pump operates with selector
switch in Hand position but will
not operate in Auto position.
1.  This  indicates  trouble  in  the

float  level  control  or  the 
alternator relay.

2.  To  check  for  defective  3900

control,  put  selector  switch  in
Auto  position  and  turn  off
main  power.  Put  a  jump  wire
between  2  and  3  on  terminal
strip.  Turn  on  power  and  if
pump  starts,  trouble  is  in  the
lower  3900  control.  Replace
control.

    If pump does not start turn off

power,  remove  jumper  from  2
and  3  and  put  jumper  wire
between 1 and 2 terminals.

    Turn  on  power  and  if  pump

starts, trouble is in upper control.
Replace control.

    If pump does not start, turn off

power and put jumper between
2 and 3 and 1 and 2 and turn on
power.  If  pump  starts,  both
lower  and  upper  controls  are
defective. If pump still does not
start, trouble is in the alternating
relay. Replace with new relay.

Pump runs but will not shut off.
1.  Pump may be air locked. Turn

pump off and let set for several
minutes, then restart.

Pump
Troubleshooting

Pump
Maintenance

Summary of Contents for S4LRC

Page 1: ...03 315 Part 5625 315 1 2011 Pentair Pump Group Inc NOTE To the installer Please make sure you provide this manual to the owner of the equipment or to the responsible party who maintains the system Installation and Service Manual For use with product built with GE motor ...

Page 2: ...connected in series with the motor starter coil so that the starter is tripped if heat sensor opens The motor starter is equipped with 3 leg overload heaters so all normal overloads are protected by the starter IMPORTANT If Hydromatic electrical starting equipment is not supplied the heat sensor circuit must be connected in series with the starter coil or warranty on motor is void Connection diagr...

Page 3: ...low inflow capacity Electrical Control Panel It is recommended that the Hydromatic control panel be used with all pumps as proper starter heaters and connections for heat sensor wires are furnished IMPORTANT If Hydromatic electrical controls are not used and the motor fails because of improper components or if the heat sensors are not properly connected the motor guarantee is void Hydromatic elect...

Page 4: ...etimes installed without a check valve where it is desirable to self drain the discharge line to prevent freezing This can be done only with short discharge lines otherwise water will return to the sump and cause short cycling of the pump NEMA 4 Junction Box Optional If electrical control panel is to be set remote from the pump sump a NEMA 4 junction box should be used to make power and control co...

Page 5: ...a see Addendum S4LRC 701 Heat Sensors and Seal Failure Connections Be sure that heat sensor wires are connected in series with the starter coil Connections are provided on the terminal strip see wiring diagram If seal failure unit is used connect as shown with seal failure system If seal failure unit is not used the two seal failure wires are left open Do not connect power to these lines at any ti...

Page 6: ...ightning occurs it is recommended that a lightning arrestor be installed at the control panel Complete data on lightning arrestors and cost are available from the factory Lightning arrestors are good insurance against damage to an expensive motor Servicing Instructions WARNINg Before handling these pumps and controls always disconnect the power first Do not smoke or use sparkable electrical device...

Page 7: ... into the stator This holding spot is drilled through the bolt hole when the stator is bolted in place with the end ring 11 Replace stator housing onto seal chamber and bolt in place BE SURE SEAL FAILURE WIRE IS CONNECTED BEFORE HOUSINg IS ASSEMBLED Be sure back off screws have been loosened so that parts can come metal to metal Be sure O ring seal has been replaced If O ring is nicked or cut repl...

Page 8: ...Megger for grounds before operating the pump Below is a list of common problems and the probable causes WARNINg Before handling pumps and controls always disconnect power first Do not smoke or use sparkable electrical devices or flame in a septic gaseous or possible septic sump Pump will not start 1 No power to the motor Check for blown fuse or open circuit breaker 2 Selector switch may be in the ...

Page 9: ...be installed on pump side of all valves Multiply gauge pressure in pounds by 2 31 to get head in feet 5 If pump has been in service for some time and capacity falls off remove pump and check for wear or clogged impeller Motor stops and then restarts after short period but overload heaters in starter do not trip 1 This indicates heat sensors in the motor are tripping due to excessive heat Impeller ...

Page 10: ...o 20 HP 575 3 60 1750 RPM VFD Stator 1 RTF Stator 25 to 35 HP 230 460 3 60 1750 RPM VFD Stator 1 RTF Stator 25 to 35 HP 575 3 60 1750 RPM VFD Stator 1 47 RTF Rotor Shaft 2 to 5 HP 870 RPM 1 RTF Rotor Shaft 3 to 15 HP 1150 RPM 1 Ref Part Part No No Description Qty RTF Rotor Shaft 10 to 20 HP 1750 RPM 1 RTF Rotor Shaft 25 to 35 HP 1750 RPM 1 48 06000 003 5 Wire TerminalAssy Priorto5 1 78 1 06000 021...

Page 11: ...11 S4LRC 55 56 54 3 53 52 50 51 49 48 47 46 45 41 42 40 35 36 38 31 33 30 37 34 28 27 26 20 2 4 5 6 7 60 8 57 9 11 12 13 14 15 16 18 19 1 29 58 ...

Page 12: ..._____________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ __________...

Page 13: ...__________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ _____________...

Page 14: ...rdance with the printed instructions provided b to failures resulting from abuse accident or negligence c to normal maintenance services and parts used in connection with such service d to units which are not installed in accordance with applicable local codes ordinances and good trade practices e if the unit is moved from its original installation location f if unit is used for purposes other tha...

Page 15: ......

Page 16: ...g Line Voltage _________________________________Actual ___________________________________ Voltage to Pumps _____________________________________Actual ___________________________________ Type of Junction Box __________________________________Manufacturer of Junction Box ______________ Are Floats Installed in Wet Well Yes No Are Floats Set to Engineer s Specs Yes No Are Floats Wired for Proper Seq...

Reviews: