23
3. Compressor
accumulations
of liquid and oil lead to the
current becomes larger
4. Compressor or driver board
damaged
5. The water flow is abnormal
6. Power fluctuations within a
short time
EE 08
Communication
failure between the
controller and the
main board
1. Poor signal wire connection
or damaged signal wire
2. Controller malfunction
1. Check and re-connect the signal wire
2. Change a new signal wire
3. Turn off electricity supply and restart
machine
4. Change a new controller
EE 09
Communication
failure between
Main board and
driver board
1. Poor
connection
of
communication wire
2. The wire is damaged
1. Check the wire connection
2. Change a new wire
EE 10
VDC voltage too
high protection
1. Mother line voltage is too
high
2. Driver board is damaged.
1. Check if the power is in the normal
range
2. Change driver board or main board
EE 11
IPM module
protection
1. Data mistake
2. Wrong compressor phase
connection
3. Compressor liquid and oil
accumulation
lead
to
the
current becomes larger
4. Compressor or driver board
damaged
1. Program error, turn off electricity
supply and restart after 3 minutes
2. Change driver board
3. Check
compressor
sequence
connection
EE 12
VDC voltage too low
protection
1. Mother line voltage is too
low
2. Driver board is damaged.
1. Check if the power is in the normal
range
2. Change driver board
EE 13
Input current over
high protection.
1. The compressor current is
too large momentary
2. The water flow is abnormal
3. Power fluctuations within a
short time
4. Wrong PFC inductor
1. Check the compressor
2. Check the waterway system
3. Check if the power is in the normal
range
4. Check if the correct PFC inductor is
used
EE 14
IPM module
thermal circuit is
abnormal
1. Output abnormity of IPM
module thermal circuit
2. Fan motor is abnormal or
damaged
3. Fan blade is broken
1. Change a driver board
2. Check if the motor speed is too low or
fan motor damaged, change another one
3. Change another fan blade
Summary of Contents for Inverter 12
Page 2: ......
Page 13: ...10 2 Dimension mm Hydro S Inverter 5 6 9 Hydro S Inverter 12 16 ...
Page 31: ...28 ...
Page 40: ...37 2 Dimension mm Hydro S Inverter 5 6 9 Hydro S Inverter 12 16 ...
Page 43: ...40 3 5 Arrangement typique Note Cet arrangement est seulement un exemple illustratif ...
Page 59: ...56 8 Schéma eclaté et entretien 8 1 Schéma eclaté Hydro S Inverter 5 6 9 ...
Page 60: ...57 ...
Page 69: ...66 2 Afmeting Dimension mm Hydro S Inverter 5 6 9 Hydro S Inverter 12 16 ...
Page 87: ...84 8 Open geklapt diagram en onderhoud 8 1 Open geklapt diagram Hydro S Inverter 5 6 9 12 ...
Page 88: ...85 ...
Page 97: ...94 2 Ausmaße Hydro S Inverter 5 6 9 Hydro S Inverter 12 16 ...
Page 100: ...97 3 5 Typische Anordnung Anmerkung Diese Anordnung ist nur ein illustratives Beispiel ...
Page 117: ...114 8 Explosionszeichnung und Wartung 8 1 Explosionszeichnung Hydro S Inverter 5 6 9 ...
Page 118: ...115 ...
Page 127: ...124 2 Wymiary Hydro S Inverter 5 6 9 Hydro S Inverter 12 16 ...
Page 146: ...143 8 Schemat budowy pompy 8 1 Widok urządzenia rozebranego Hydro S Inverter 5 6 9 ...
Page 147: ...144 ...
Page 156: ...153 2 Dimension mm Hydro S Inverter 5 6 9 Hydro S Inverter 12 16 ...
Page 159: ...156 3 5 typisk arrangement Bemærk Dette arrangement er kun et illustrativt eksempel ...
Page 175: ...172 ...
Page 181: ......
Page 182: ...A0111MBE01 ...